Plan Review Notes
Plan Review Notes For Permit 04021070
Permit Number 04021070
Review Stop E
Sequence Number 4
Notes
Date Text
2005-02-17 00:00:00*********UNSAT *************
  
 1)NOTE: PLEASE SEE RISER INDICATES BOTH
 PANELS AS MLO AND NO MAIN IS SHOWN?
 PLEASE SEE PLANS SHOWS A SEPARATE MAIN?
 PLEASE CORRELATE. MAIN REQUIRED
 225.31,225.32,240.4 ETC
  
 2)NOTE: PLEASE SEE RISER SHOWS SUB PANEL
 AS 60A'S YET PANEL SHOWS @ 100A'S.
 PLEASE ALSO SEE PANEL "A" SHOWS A SINGLE
 POLE 15A BRKR FEEDING PANEL "B".
 PLEASE ALSO SEE RISER INDICATES A 100A
 BRKR FEEDING THE 60A PANEL?
 PLEASE ADJUST.
  
 3)NOTE: PLEASE PANEL"A" INDICATES FOUR
 10KW AHU'S. NO COND UNITS SHOWN?
 PLEASE VERIFY AND CORRECT.
  
 4)NOTE: PLEASE SEE GFI RECEPT SPACING IN
 KITCHEN TO BE PER 210.52C1. MISSING ON
 MORE THAN ONE COUNTERSPACE.
  
 5)NOTE: PLEASE SEE 210.52D FOR GFI
 RECEPTS TO BE W/IN 3' OF BATH RM SINKS
 EDGE.
  
 6)NOTE: PLEASE SEE PLANS DO NOT INDICATE
 LOACTION OF PANEL "B".
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE SEE MISSING HALLWAY
 RECEPT PER 210.52H
  
 9)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM TO INCLUDE FOOTER STEEL PER
 250.50.
  
 ** PLEASE SEE ONE COPY OF PLANS ARE
 BEING RETAINED. PLEASE SEE OTHER COPY
 HAS MOST OF THESE ITEMS REDLINED AT
 LOCATIONS FOR ABOVE NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  