| 2005-02-17 00:00:00 | *********UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE RISER INDICATES BOTH |
| | PANELS AS MLO AND NO MAIN IS SHOWN? |
| | PLEASE SEE PLANS SHOWS A SEPARATE MAIN? |
| | PLEASE CORRELATE. MAIN REQUIRED |
| | 225.31,225.32,240.4 ETC |
| | |
| | 2)NOTE: PLEASE SEE RISER SHOWS SUB PANEL |
| | AS 60A'S YET PANEL SHOWS @ 100A'S. |
| | PLEASE ALSO SEE PANEL "A" SHOWS A SINGLE |
| | POLE 15A BRKR FEEDING PANEL "B". |
| | PLEASE ALSO SEE RISER INDICATES A 100A |
| | BRKR FEEDING THE 60A PANEL? |
| | PLEASE ADJUST. |
| | |
| | 3)NOTE: PLEASE PANEL"A" INDICATES FOUR |
| | 10KW AHU'S. NO COND UNITS SHOWN? |
| | PLEASE VERIFY AND CORRECT. |
| | |
| | 4)NOTE: PLEASE SEE GFI RECEPT SPACING IN |
| | KITCHEN TO BE PER 210.52C1. MISSING ON |
| | MORE THAN ONE COUNTERSPACE. |
| | |
| | 5)NOTE: PLEASE SEE 210.52D FOR GFI |
| | RECEPTS TO BE W/IN 3' OF BATH RM SINKS |
| | EDGE. |
| | |
| | 6)NOTE: PLEASE SEE PLANS DO NOT INDICATE |
| | LOACTION OF PANEL "B". |
| | |
| | 7 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 8)NOTE: PLEASE SEE MISSING HALLWAY |
| | RECEPT PER 210.52H |
| | |
| | 9)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM TO INCLUDE FOOTER STEEL PER |
| | 250.50. |
| | |
| | ** PLEASE SEE ONE COPY OF PLANS ARE |
| | BEING RETAINED. PLEASE SEE OTHER COPY |
| | HAS MOST OF THESE ITEMS REDLINED AT |
| | LOCATIONS FOR ABOVE NOTES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |