| Plan Review Notes For Permit 04021070 |
| Permit Number |
04021070 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-03 00:00:00 | DENIED: | | | 2ND REQUEST: | | | 1.PROVIDE ENERGY AND MANUAL J | | | CALCULATIONS PER 2001 FBC CHAPTER 13. | | | | | | 1ST REQUEST: | | | 1.BEDROOM #2 MISSING RETURN AIR DUCT | | | & GRILLE SIZE & LAYOUT. | | | | | | 2.SUPPLY DUCT TO BEDROOM #3 IS NOT | | | SIZED.PLEASE REVISE. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 4.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 402.2 OR 403.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|