| 2004-04-23 00:00:00 | ************** UNSAT 2ND TIME ********* |
| | |
| | PLEASE SEE MOST COMMENTS FROM FIRST |
| | REVIEW HAVE NOT BEEN ADRESSED FOR CODE |
| | COMPLIANCE. |
| | |
| | 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 2 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E PLANS SHOW TWO SEPARATE GFI |
| | RECEPTS FOR A/C COND UNITS?? |
| | MISSING FRONT OF DWELLING. |
| | |
| | 3 )NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLANS STILL MISSING ONES FROM FIRST |
| | REVIEW. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | SHOWN FOR SUB PANELS, BUT NOT FOR MAIN. |
| | |
| | 5)NOTE: PLEASE SEE RISER, PLEASE SEE |
| | 250.6, 250.24. AN EQUIPMENT GROUDING |
| | CONDUCTOR AS SHOWN SHALL NOT BE INSTALL- |
| | ED AND MUST BE REMOVED. |
| | |
| | 6)NOTE: PLEASE SEE PANEL SCHEDULES. |
| | THERE ARE MANY 220V/2-POLE ITEMS SHOWN |
| | AS 1-POLE BRKRS? MISPRINT? |
| | |
| | 7)NOTE: PLEASE SEE PLANS NOW REFERENCE |
| | THE FBC FOR ARC FAULT PROTECTION. |
| | 210.12 FOR ARC FAULT PROETCTION IS FROM |
| | THE 2002 NEC. |
| | |
| | 8 )NOTE: PLEASE CORRELATE RISER DIGRAM(S |
| | WITH PANEL SCHEDULE(S). |
| | RISER SHOWS #3 FOR CONDUCTORS TO SUB |
| | PANEL. PLEASE INDICATE # OF #3'S. |
| | |
| | 9)NOTE: PLEASE SEE NOTE #9 MENTIONS: |
| | ALL CONDUCTORS TO BE #12, YET PANEL |
| | SCHEDULES INDICATE #14'S???? |
| | |
| | 10)NOTE: PLEASE SEE RECEPT IN MASTERBATH |
| | DOES NOT MEET 210.52D. |
| | |
| | 11)NOTE: PLEASE SEE FS 481.219 AND |
| | FAC 61G1-16.004. PLEASE INCLUDE ALL |
| | LICENSE #'S REQ'D IN TITLE BLOCK. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTH- |
| | -ORIZATION #. |
| | |
| | 12) NOTE: PLEASE SHOW LOAD CALCS AS |
| | REQ'D UNDER NEC 220. PLEASE SHOW ALL MIN |
| | CIRCUITS AND LOADS. 215.5 |
| | |
| | 13)NOTE: PLEASE SEE NOTICE IS NOW GIVEN |
| | FOR FS 553.80(2)(B). |
| | IF PLANS COME BACK FOR 3RD REVIEW AND |
| | ANY OF THE SAME COMMENTS FROM THE FIRST |
| | TWO REVIEWS FOR CODE COMPLIANCE ARE NOT |
| | ADDRESSED, A 4X FEE WILL BE ACCESSED |
| | FOR PLAN REVIEW PORTION. |
| | |
| | 14)NOTE: PLEASE SHOW SUB PANEL "B" ON |
| | PLANS. ONLY PANEL "A" IS SHOWN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |