2004-04-23 00:00:00************** UNSAT 2ND TIME *********
  
 PLEASE SEE MOST COMMENTS FROM FIRST
 REVIEW HAVE NOT BEEN ADRESSED FOR CODE
 COMPLIANCE.
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 2 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E PLANS SHOW TWO SEPARATE GFI
 RECEPTS FOR A/C COND UNITS??
 MISSING FRONT OF DWELLING.
  
 3 )NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLANS STILL MISSING ONES FROM FIRST
 REVIEW.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR SUB PANELS, BUT NOT FOR MAIN.
  
 5)NOTE: PLEASE SEE RISER, PLEASE SEE
 250.6, 250.24. AN EQUIPMENT GROUDING
 CONDUCTOR AS SHOWN SHALL NOT BE INSTALL-
 ED AND MUST BE REMOVED.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULES.
 THERE ARE MANY 220V/2-POLE ITEMS SHOWN
 AS 1-POLE BRKRS? MISPRINT?
  
 7)NOTE: PLEASE SEE PLANS NOW REFERENCE
 THE FBC FOR ARC FAULT PROTECTION.
 210.12 FOR ARC FAULT PROETCTION IS FROM
 THE 2002 NEC.
  
 8 )NOTE: PLEASE CORRELATE RISER DIGRAM(S
 WITH PANEL SCHEDULE(S).
 RISER SHOWS #3 FOR CONDUCTORS TO SUB
 PANEL. PLEASE INDICATE # OF #3'S.
  
 9)NOTE: PLEASE SEE NOTE #9 MENTIONS:
 ALL CONDUCTORS TO BE #12, YET PANEL
 SCHEDULES INDICATE #14'S????
  
 10)NOTE: PLEASE SEE RECEPT IN MASTERBATH
 DOES NOT MEET 210.52D.
  
 11)NOTE: PLEASE SEE FS 481.219 AND
 FAC 61G1-16.004. PLEASE INCLUDE ALL
 LICENSE #'S REQ'D IN TITLE BLOCK.
 PLEASE SEE MISSING CERTIFICATE OF AUTH-
 -ORIZATION #.
  
 12) NOTE: PLEASE SHOW LOAD CALCS AS
 REQ'D UNDER NEC 220. PLEASE SHOW ALL MIN
 CIRCUITS AND LOADS. 215.5
  
 13)NOTE: PLEASE SEE NOTICE IS NOW GIVEN
 FOR FS 553.80(2)(B).
 IF PLANS COME BACK FOR 3RD REVIEW AND
 ANY OF THE SAME COMMENTS FROM THE FIRST
 TWO REVIEWS FOR CODE COMPLIANCE ARE NOT
 ADDRESSED, A 4X FEE WILL BE ACCESSED
 FOR PLAN REVIEW PORTION.
  
 14)NOTE: PLEASE SHOW SUB PANEL "B" ON
 PLANS. ONLY PANEL "A" IS SHOWN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  