| 2004-03-01 00:00:00 | DENIED |
| | ~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE FEEDER FROM PANEL "A" TO PANEL |
| | "B"ON THE RISER DIAGRAM IS 3/0 AND |
| | #3 ON THE PANEL SCHEDULE.PLEASE |
| | CORRELATE. |
| | |
| | 2} PANEL "B"IS MARKED PANEL"A" ON THE |
| | RISER DIAGRAM. |
| | |
| | 3} PLEASE NOTE THAT THE SMOKE DETECTORS |
| | MUST BE ON AN ARC FAULT BREAKER PER |
| | 210.12, SEE DEFINITION OF OUTLETS" IN |
| | ARTICLE 100 NEC. |
| | |
| | 4} THE RECEPTACLE IN THE MASTER BATH |
| | DOES NOT COMPLY WITH 210.52(D),IT'S |
| | MORE THAN 3' FROM THE BASIN. |
| | |
| | 5} THERE ARE 2 PLACES ON THE KITCHEN |
| | COUNTERTOP THAT NEED ANOTHER |
| | RECEPTACLE PER 210.52(C)(1). |
| | |
| | 6} THE ISLAND IN THE KITCHEN NEEDS A |
| | RECEPTACLE PER 210.52(C)(2). |
| | |
| | 7) THE LOCATION OF THE A/C DISCONNECTS |
| | DO NOT COMPLY WITH 110.26 FOR CLEARANCE. |
| | |
| | 8} A RECEPTACLE AT THE FRONT OF THE |
| | DWELLING MUST BE ADDED PER 210.52(E). |
| | |
| | 9} PLEASE NOTE THAT THE ARCHITECTS |
| | SIGNATURE IS REQUIRED ON HIS/HER SEAL |
| | PER 61G116.003.INITIALS ARE NOT |
| | ACCEPTABLE. |
| | |
| | ONE SET OF THE PLANS SUBMITTED HAVE BEEN |
| | REVIEWED AND CODE ARTICLES PER COMMENTS |
| | ARE MARKED ON THE PLANS. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |