Plan Review Notes
Plan Review Notes For Permit 04021070
Permit Number 04021070
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-01 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDER FROM PANEL "A" TO PANEL
 "B"ON THE RISER DIAGRAM IS 3/0 AND
 #3 ON THE PANEL SCHEDULE.PLEASE
 CORRELATE.
  
 2} PANEL "B"IS MARKED PANEL"A" ON THE
 RISER DIAGRAM.
  
 3} PLEASE NOTE THAT THE SMOKE DETECTORS
 MUST BE ON AN ARC FAULT BREAKER PER
 210.12, SEE DEFINITION OF OUTLETS" IN
 ARTICLE 100 NEC.
  
 4} THE RECEPTACLE IN THE MASTER BATH
 DOES NOT COMPLY WITH 210.52(D),IT'S
 MORE THAN 3' FROM THE BASIN.
  
 5} THERE ARE 2 PLACES ON THE KITCHEN
 COUNTERTOP THAT NEED ANOTHER
 RECEPTACLE PER 210.52(C)(1).
  
 6} THE ISLAND IN THE KITCHEN NEEDS A
 RECEPTACLE PER 210.52(C)(2).
  
 7) THE LOCATION OF THE A/C DISCONNECTS
 DO NOT COMPLY WITH 110.26 FOR CLEARANCE.
  
 8} A RECEPTACLE AT THE FRONT OF THE
 DWELLING MUST BE ADDED PER 210.52(E).
  
 9} PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 ONE SET OF THE PLANS SUBMITTED HAVE BEEN
 REVIEWED AND CODE ARTICLES PER COMMENTS
 ARE MARKED ON THE PLANS. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026