| 2004-04-01 00:00:00 | BUILDING PLAN REVIEW FAILED: |
| | |
| | 1. IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | A COPY OF THE PAID RECEIPT SUBMITTED TO |
| | THE CITY BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2. A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3. SUBMIT A SIGNED & SEALED COPY OF THE |
| | SOIL REPORT INCLUDING THE BORING LOG. |
| | |
| | 4. THE GLASS BLOCK IN THE EXTERIORWALL |
| | THAT IS WITHIN 3 FEET OF THE PROPERTY |
| | LINE IS REQUIRED TOHAVE |
| | A ONE HOUR FIRE RATING PER FBC TABLE |
| | 600. SPECIFY ON PLANS. |
| | |
| | 5. THE GLASS BLOCK AT THE TUBS IN THE |
| | MASTER BATH & BATH #2 IS REQUIRED TO |
| | HAVE A MINIMUM UNIFORM FACE THICKNESS |
| | OF 0.25. SEE FBC 2405.2.2 (5) |
| | |
| | 6. THE WINDOW IN BATH #3 IS WITHIN 3' |
| | OF SHOWER IS REQUIRED TO HAVE SAFETY |
| | GLAZING PER 2405.2. |
| | |
| | 7.PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | ATWWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | SUBMIT STATE OR LOCAL PRODUCT APPROVALS |
| | FOR THE FOLLOWING: |
| | ROOF TILE |
| | DOUBLE INSWING ENTRY DOORS |
| | DOUBLE OUTSWING GLAZED DOORS WITH AND |
| | WITHOUT SIDELIGHTS. |
| | SINGLE OUTSWING PANEL DOORS |
| | SINGLE HUNG WINDOWS |
| | FIXED GLASS WINDOWS (CIRCULAR, ARCHED, |
| | ETC. |
| | GLASS BLOCK ( FIRE RATED) |
| | STRUCTURAL MULLIONS |
| | OVERHEAD GARAGE DOORS |
| | STORM PANELS |
| | TRUSS ANCHORS & CONNECTORS. |
| | |
| | 8. SUBMIT MANUFACTURER'S INSTALLATION |
| | SPECIFICATIONS AND LISTING FOR ONE HOUR |
| | GLASS BLOCK ASSEMBLY. |
| | |
| | 9. SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS.SPECIFY |
| | THE MOUNT TYPE, ANCHOR TYPE AND SPACING |
| | ON THE INSTALLATION DRAWINGS. |
| | |
| | 10. 2 DIFFERENT PRODUCT APPROVALS (DADE |
| | COUNTY) WERE SUBMITTED FOR THE ROOF. |
| | PLEASE REMOVE ONE. A SEPARATE |
| | PERMIT WILL BE REQUIRED FOR THE ROOF. |
| | |
| | 11. SUBMITTALS FOR BUTT GLASS WAS |
| | SUBMITTED.PLANS DO NOT SHOW ANY BUTT |
| | GLASS WINDOWS IN THIS HOUSE. |
| | |
| | 12. SUBMIT 2 COPIES OF THE |
| | MANUFACTURER'S SPECIFICATIONS AND UL |
| | LISTING FOR THE GAS BBQ AND HOOD.A |
| | SEPARATE GAS PERMIT WILL BE REQUIRED. |
| | |
| | 13. KITCHEN WINDOW DIMENSIONS NOT SHOWN |
| | ON PLANS. (ONLY TRANSOM SHOWN) |
| | |
| | 14. THE FBC TABLE 600 CALCULATIONS FOR |
| | THE EXTERIOR WALL AT THE DINING ROOM AND |
| | DEN/STUDY ARE INCORRECT. ONLY 20% OF |
| | THE WALL AREA IS ALLOWED AS OPENINGS. |
| | PLEASE CORRECT. |
| | |
| | 15. SPECIFY THE FOOTING DETAIL FOR THE |
| | 5' WALL IN THE GARDEN COURT. |
| | |
| | 16. THE STATEDVALUE OF THE HOUSE IS |
| | UNDERSTATED.VALUE HAS BEEN ADJUSTED |
| | TO $290,601. PER SBCCI BUILDING |
| | VALUATION DATA. |
| | |
| | ANY QUESTIONS PLEASE CALL: |
| | LEA SMITH, BUILDING PLANS EXAMINER |
| | 805-6713 |