2004-04-01 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 A COPY OF THE PAID RECEIPT SUBMITTED TO
 THE CITY BEFORE A PERMIT CAN BE ISSUED.
  
 2. A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3. SUBMIT A SIGNED & SEALED COPY OF THE
 SOIL REPORT INCLUDING THE BORING LOG.
  
 4. THE GLASS BLOCK IN THE EXTERIORWALL
 THAT IS WITHIN 3 FEET OF THE PROPERTY
 LINE IS REQUIRED TOHAVE
 A ONE HOUR FIRE RATING PER FBC TABLE
 600. SPECIFY ON PLANS.
  
 5. THE GLASS BLOCK AT THE TUBS IN THE
 MASTER BATH & BATH #2 IS REQUIRED TO
 HAVE A MINIMUM UNIFORM FACE THICKNESS
 OF 0.25. SEE FBC 2405.2.2 (5)
  
 6. THE WINDOW IN BATH #3 IS WITHIN 3'
 OF SHOWER IS REQUIRED TO HAVE SAFETY
 GLAZING PER 2405.2.
  
 7.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 ATWWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT STATE OR LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING:
 ROOF TILE
 DOUBLE INSWING ENTRY DOORS
 DOUBLE OUTSWING GLAZED DOORS WITH AND
 WITHOUT SIDELIGHTS.
 SINGLE OUTSWING PANEL DOORS
 SINGLE HUNG WINDOWS
 FIXED GLASS WINDOWS (CIRCULAR, ARCHED,
 ETC.
 GLASS BLOCK ( FIRE RATED)
 STRUCTURAL MULLIONS
 OVERHEAD GARAGE DOORS
 STORM PANELS
 TRUSS ANCHORS & CONNECTORS.
  
 8. SUBMIT MANUFACTURER'S INSTALLATION
 SPECIFICATIONS AND LISTING FOR ONE HOUR
 GLASS BLOCK ASSEMBLY.
  
 9. SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS.SPECIFY
 THE MOUNT TYPE, ANCHOR TYPE AND SPACING
 ON THE INSTALLATION DRAWINGS.
  
 10. 2 DIFFERENT PRODUCT APPROVALS (DADE
 COUNTY) WERE SUBMITTED FOR THE ROOF.
 PLEASE REMOVE ONE. A SEPARATE
 PERMIT WILL BE REQUIRED FOR THE ROOF.
  
 11. SUBMITTALS FOR BUTT GLASS WAS
 SUBMITTED.PLANS DO NOT SHOW ANY BUTT
 GLASS WINDOWS IN THIS HOUSE.
  
 12. SUBMIT 2 COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS AND UL
 LISTING FOR THE GAS BBQ AND HOOD.A
 SEPARATE GAS PERMIT WILL BE REQUIRED.
  
 13. KITCHEN WINDOW DIMENSIONS NOT SHOWN
 ON PLANS. (ONLY TRANSOM SHOWN)
  
 14. THE FBC TABLE 600 CALCULATIONS FOR
 THE EXTERIOR WALL AT THE DINING ROOM AND
 DEN/STUDY ARE INCORRECT. ONLY 20% OF
 THE WALL AREA IS ALLOWED AS OPENINGS.
 PLEASE CORRECT.
  
 15. SPECIFY THE FOOTING DETAIL FOR THE
 5' WALL IN THE GARDEN COURT.
  
 16. THE STATEDVALUE OF THE HOUSE IS
 UNDERSTATED.VALUE HAS BEEN ADJUSTED
 TO $290,601. PER SBCCI BUILDING
 VALUATION DATA.
  