2004-06-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} BEDROOM #2 NEEDS A RECEPTACLE TO
 COMPLY WITH 210.52(A)(2).
  
 2} A SMOKE DETECTOR IS REQUIRED OUTSIDE
 BEDROOM #3 PER 8-1.4.1.6.2(1) NFPA-72.
  
 3} THE DISCONNECT LOCATION FOR CU #2
 STILL WILL NOT COMPLY WITH 110.26
 CLEARANCE DUE TO THE WALL LOCATION
 ENCLOSING THE UNITS.
  
 4} THE ARCHITECTS AA NUMBER IN THE TITLE
 BLOCK IS NOT LISTED WITH THE DBPR.
  