| 2004-03-01 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE RISER DIAGRAM INDICATES #3/0 |
| | FEEDERS TO THE 100 AMP PANEL(MARKED |
| | "A"ON THE RISER) AND #3'S ON THE PANEL |
| | SCHEDULE, PLEASE CORRELATE. |
| | |
| | 2} THE "BREAKFAST" AND "BEDROOM #3 NEED |
| | RECEPTACLES ADDED TO COMPLY WITH |
| | 210.52(A)(2). |
| | |
| | 3} THE KITCHEN COUNTERTOP NEEDS A |
| | RECEPTACLE TO COMPLY WITH 210.52(C)(1). |
| | |
| | 4} THE GUEST BEDROOM(LABLED BEDROOM#3 |
| | ON ELECTRICAL PLAN) NEEDS A SMOKE |
| | DETECTOR IN THE HALLWAY OUTSIDE IN THE |
| | "IMMIDIATE VICINITY" TO COMPLY WITH |
| | 8-1.4.1.6.2 NFPA-72. |
| | |
| | 5} THE A/C DISCONNECT LOCATIONS DO NOT |
| | COMPLY WITH 110.26. |
| | |
| | 6} PLEASE SEE 210.12 WHICH INDICATES |
| | THAT THE SMOKE DETECTORS MUST ALSO BE |
| | ARC FAULT PROTECTED.SEE THE DEFINITION |
| | OF "OUTLET" IN ARTICLE 100,NEC. |
| | |
| | ALL OF THE ABOVE CORRECTIONS ARE MARKED |
| | ON ONE SET OF REVIEWED PLANS FOR |
| | REFERENCE. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | PLEASE NOTE THAT THE ARCHITECTS |
| | SIGNATURE IS REQUIRED ON HIS/HER SEAL |
| | PER 61G116.003.INITIALS ARE NOT |
| | ACCEPTABLE. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |