2004-03-01 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM INDICATES #3/0
 FEEDERS TO THE 100 AMP PANEL(MARKED
 "A"ON THE RISER) AND #3'S ON THE PANEL
 SCHEDULE, PLEASE CORRELATE.
  
 2} THE "BREAKFAST" AND "BEDROOM #3 NEED
 RECEPTACLES ADDED TO COMPLY WITH
 210.52(A)(2).
  
 3} THE KITCHEN COUNTERTOP NEEDS A
 RECEPTACLE TO COMPLY WITH 210.52(C)(1).
  
 4} THE GUEST BEDROOM(LABLED BEDROOM#3
 ON ELECTRICAL PLAN) NEEDS A SMOKE
 DETECTOR IN THE HALLWAY OUTSIDE IN THE
 "IMMIDIATE VICINITY" TO COMPLY WITH
 8-1.4.1.6.2 NFPA-72.
  
 5} THE A/C DISCONNECT LOCATIONS DO NOT
 COMPLY WITH 110.26.
  
 6} PLEASE SEE 210.12 WHICH INDICATES
 THAT THE SMOKE DETECTORS MUST ALSO BE
 ARC FAULT PROTECTED.SEE THE DEFINITION
 OF "OUTLET" IN ARTICLE 100,NEC.
  
 ALL OF THE ABOVE CORRECTIONS ARE MARKED
 ON ONE SET OF REVIEWED PLANS FOR
 REFERENCE. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  