| 2004-03-05 00:00:00 | ******** UNSAT ************ | | | | | | 1)NOTE: CIRCUITS FOR RECEPTS ARE | | | SHOWN 3OR SO PER GROUP. PLEASE PROVIDE | | | NOTE, TO MAX AMOUNT PER CIRCUIT. | | | | | | 2)NOTE: PLEASE SEE ELECTRICAL PLANS, | | | PLANS DO NOT INDICATE/SHOW ELECTRICAL | | | PANEL/TRANSFORMER LOCATION. PLEASE | | | SHOW LOCATION OF ELECTRICAL ROOM. | | | IS THIS LOCATION ACCROSS HALL AS SHOWN | | | ON ARCH? PLEASE SHOW EQUIPMENT ON LAYOUT | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3,230.42 ETC. | | | | | | PLEASE VERIFY LOAD ON EXSITNG SERVICE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|