| Plan Review Notes For Permit 04021037 |
| Permit Number |
04021037 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04021037 | | | ADD: 326 FERN ST# 301 | | | CONT: CATALFUMO | | | TEL: (561)307-4836 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THE OCCUPANCY IS CORRECT AS BUSINESS | | | BUT THE CONFRENCE ROOM IS CONSIDERED TO | | | BE ASSEMBLY AS FAR AS OCCUPANT LOAD. | | | CONFERENCE ROOMS USE 15 NET, THE OCCU- | | | PANT LOAD FOR THIS ROOM IS 71.DOOR 317 & | | | 318 NEED TO HAVE THE DOOR SWING REVERSED | | | 1012.1.2 EGRESS DOORS SHALL BE SIDE | | | SWINGING TYPE, DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS. | | | | | | 2) THIS SAME ISSUE WILL ALSO HOLD TRUE | | | FOR THE MOVED DOORS#300 & 306, | | | REVERSE SWING IN THE DIRECTION OF | | | TRAVEL. | | | | | | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|