2004-03-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021037
 ADD: 326 FERN ST# 301
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE OCCUPANCY IS CORRECT AS BUSINESS
 BUT THE CONFRENCE ROOM IS CONSIDERED TO
 BE ASSEMBLY AS FAR AS OCCUPANT LOAD.
 CONFERENCE ROOMS USE 15 NET, THE OCCU-
 PANT LOAD FOR THIS ROOM IS 71.DOOR 317 &
 318 NEED TO HAVE THE DOOR SWING REVERSED
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE, DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS.
  
 2) THIS SAME ISSUE WILL ALSO HOLD TRUE
 FOR THE MOVED DOORS#300 & 306,
 REVERSE SWING IN THE DIRECTION OF
 TRAVEL.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026