Plan Review Notes
Plan Review Notes For Permit 04021011
Permit Number 04021011
Review Stop B
Sequence Number 2
Notes
Date Text
2004-04-21 00:00:00DENIED
  
 1) ON SHEET A5 UNDER STRUCTURAL DESIGN
 CRITERIA THE MEAN ROOF HEIGHT IS LISTED
 AS + OR - 10 FEET. THE MEAN ROOF HEIGHT
 IS THE DISTANCE FROM GRADE TO THE
 AVERAGE HEIGHT OF THE HIGHEST ROOF
 HAVING A PITCH. FOR THIS STRUCTURE IT IS
 MORE THAN 10 FEET. PLEASE CORRECT.
  
 2) SOME OF THE ANCHORS IN THE LEGEND ON
 SHEET A5 HAVE UPLIFT VALUES SPECIFIED
 WHICH INCLUDE THE ONE THIRD STRESS
 INCREASE IN THE STEEL CALCULATIONS,
 WHICH IS NOT ALLOWED BY FBC 1609.3. THE
 UPLIFT VALUES LISTED FOR ID TAG NUMBERS
 (1B) AND (2) FOR THE TA20R CONNECTORS
 ARE INCORRECT. SEE 2004 USP CATALOG FOR
 VALUES THAT DO NOT INCLUDE A STRESS
 INCREASE ON THE STEEL CALCULATIONS.
  
 3) THE UPLIFT AND ANCHOR KEY IN THE
 ANCHOR LEGEND SPECIFIES THE UPLIFT
 VALUES ON THE BOTTOM AND THE ANCHOR ON
 TOP. HOWEVER, ON THE ROOF FRAMING PLAN
 THESE ITEMS ARE REVERSED IN THE ID TAGS.
  
 4) THE STATE PRODUCT APPROVAL FOR THE
 HANSON ROOF TILE IS REQUIRED TO HAVE THE
 SBCCI PST AND ESI REPORTS SUBMITTED
 BECAUSE THEY WERE THE EVALUATION ENTITY
 USED FOR STATE APPROVAL. THE SUBMITTAL
 FOR THE MONIER LIFETILE IS OK. PLEASE
 SELECT THE ONE THAT WILL BE INSTALLED
 AND REMOVE THE OTHER FROM THE SUBMITTAL.
  
 5) SUBMIT STATE PRODUCT APPROVALS FOR
 THE DOUBLE OUTSWING FRENCH DOORS WITH
 SIDELITES. THE PRODUCT APPROVAL FL 1433
 THAT WAS SUBMITTED DOES HAVE THE TESTING
 REPORT (EVALUATION METOD) INDICATING THE
 DESIGN PRESSURES AND LIMITATIONS AND THE
 INSTALLATION INSTRUCTIONS.
  
 6) SUBMIT STATE PRODUCT APPROVALS FOR
 IMPACT RATED ENTRY DOORS, WHICH IS
 REQUIRED FOR EMERGENCY EGRESS PER FBC
 1005.4.5.
  
 7) SUBMIT (2) COPIES OF THE RECORDED
 EASEMENT RELEASE FOR THE 2.5' SHOWN ON
 THE SURVEY IN A DRAINAGE EASEMENT.
  
 8)SUBMIT STATE OR LOCAL PRODUCT APPROVAL
 FOR THE BUTT GLASS WINDOW.
  
 9)SUBMIT STATE OR LOCAL PRODUCT APPROVAL
 FOR THE 12' STRUCTURAL MULLION BETWEEN
 THE FRENCH DOORS WITH SIDELITES AND THE
 TRANSOM ABOVE OR REVISE PLANS TO SHOW A
 BEAM OR LINTEL BETWEEN THE OPENINGS.
  
 10) ONLY TWO COPIES OF SUBMITTAL ITEMS
 ARE REQUIRED. PLEASE REMOVE ALL EXTRA
 COPIES FROM THE PACKAGE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714