| Plan Review Notes For Permit 04020937 |
| Permit Number |
04020937 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-24 00:00:00 | DENIED: | | | PLEASE INDICATE SCOPE OF WORK WITH THIS | | | PERMIT APPLICATION. | | | 1.PLEASE PROIVDE OUTSIDE AIR | | | CALCULATIONS FOR EACH TENANT SUBMITTED | | | UNDER THIS PERMIT. | | | | | | 2.PROVIDE SPECIFIC INFORMATION ON THE | | | EQUIPMENT.EQUIPMENT SCHEDULE | | | INDICATES 2 - 5 TON SYSTEMS, PLEASE | | | CLARIFY. | | | | | | 3.ENERGY CALCULATIONS NOT SUBMITTED, | | | WAS THIS PROVIDED WITH ANOTHER PERMIT? | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED FOR AHU-1. 2001 | | | FBC(M) 307.2.3. | | | | | | SPOKE WITH JEFF BERKUN, ENGINEER CAN DO | | | THE ABOVE REQUIREMENTS WITH A SIGNED, | | | SEALED AND DATED LETTER.TWO COPIES | | | REQUIRED.PLANS ARE OTHERWISE CODE | | | COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|