2005-01-31 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SUBMIT TWO COPIES OF
 MANUFACTURE SPECS FOR GENERATOR/TRANSFER
 SWITCH ETC.
 PLEASE SEE ZONING NOTES FOR SURVEY AND
 SET BACKS.
 ONLY ONE COPY OF SURVEY SUBMITTED.
  
 2)NOTE: PLEASE SEE 700.6 FOR TRANSFER OF
 POWER FOR EM POWER. TRANSFER OF POWER
 SHOWN ON RISER IS NOT PERMITTED.
 A FAIL SAFE MANNER IS REQUIRED.
  
 3)NOTE: PLEASE SEE BLDG C.O. HAS BEEN
 REVOKED AND DATE REMOVED. PLEASE SEE NOT
 ONLY DO PLANS NEED TO BE REVISED, BUT
 THERE MAY BE A NEED FOR A RE-INSPECTION
 OF ELECTRICAL EQUIPMENT/SET BACK ETC.
  
 4)NOTE: PLEASE SEE MECH NOTES, FOR
 GENERATOR TO BE A MIN OF 10' FROM
 OPENINGS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  