Plan Review Notes
Plan Review Notes For Permit 04020930
Permit Number 04020930
Review Stop E
Sequence Number 2
Notes
Date Text
2004-12-02 00:00:00 
 ALL CHANGES TO PLANS MUST BE DONE BY
 THEDESIGNER OF RECORD. HAND DRAWN
 CHANGESARE NOT ACCEPTABLE. THE
 ARCHITECT WHO SIGNED THIS PLAN IS NOT
 THE ORIGINAL ARCHITECT IN VIOLATION OF
 ARTICLE 481.221(1)(A)(4), FLORIDA
 STATUTES.
  
 THE GAS GENERATOR SHOWN ON THE ATTACHED
 RISER DIAGRAM WAS NOT PERMITTED. SUBMIT
 ALL RELATED DRAWINGS FOR SAME AS A
 REVISION TO THIS PLAN OR UNDER A NEW
 APPLICATION. THESE PLANS MUST INCLUDE
 WIRING DIAGRAMS, ALL PANELS AND TRANSFER
 SWITCHES AND RELATED EQUIPMENT. ALSO
 SUBMIT A CURRENT SURVEY SHOWINGLOCATION
 OF SAME FOR ZONING REVIEW. A GAS PERMIT
 IS ALSO REQUIRED. THE COST OF THE
 EQUIPMENT AS WELL AS LABOR MUST BE
 SHOWN AND THE VALUE OF THE JOB MUST BE
 INCREASED TO REFLECT SAME.
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.PER 110.9/215.5. SUBMIT PANEL
 SCHEDULES FOR ALL PANELS. INCREASE VALUE
 TO REFLECT LABOR & EQUIPMENT PER
 104.6.5
 FBC.
  
 PROVIDE LOAD CALCULATIONS FOR ALL LOADS
 INCLUDING ADDED AND EXISTING A/C, &
 BOTH TANKLESS UNITS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  