| 2004-12-02 00:00:00 | |
| | ALL CHANGES TO PLANS MUST BE DONE BY |
| | THEDESIGNER OF RECORD. HAND DRAWN |
| | CHANGESARE NOT ACCEPTABLE. THE |
| | ARCHITECT WHO SIGNED THIS PLAN IS NOT |
| | THE ORIGINAL ARCHITECT IN VIOLATION OF |
| | ARTICLE 481.221(1)(A)(4), FLORIDA |
| | STATUTES. |
| | |
| | THE GAS GENERATOR SHOWN ON THE ATTACHED |
| | RISER DIAGRAM WAS NOT PERMITTED. SUBMIT |
| | ALL RELATED DRAWINGS FOR SAME AS A |
| | REVISION TO THIS PLAN OR UNDER A NEW |
| | APPLICATION. THESE PLANS MUST INCLUDE |
| | WIRING DIAGRAMS, ALL PANELS AND TRANSFER |
| | SWITCHES AND RELATED EQUIPMENT. ALSO |
| | SUBMIT A CURRENT SURVEY SHOWINGLOCATION |
| | OF SAME FOR ZONING REVIEW. A GAS PERMIT |
| | IS ALSO REQUIRED. THE COST OF THE |
| | EQUIPMENT AS WELL AS LABOR MUST BE |
| | SHOWN AND THE VALUE OF THE JOB MUST BE |
| | INCREASED TO REFLECT SAME. |
| | |
| | NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT.PER 110.9/215.5. SUBMIT PANEL |
| | SCHEDULES FOR ALL PANELS. INCREASE VALUE |
| | TO REFLECT LABOR & EQUIPMENT PER |
| | 104.6.5 |
| | FBC. |
| | |
| | PROVIDE LOAD CALCULATIONS FOR ALL LOADS |
| | INCLUDING ADDED AND EXISTING A/C, & |
| | BOTH TANKLESS UNITS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |