| Plan Review Notes For Permit 04020849 |
| Permit Number |
04020849 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-06-16 00:00:00 | | | | THE ARCHITECT MUST MAKE ALL | | | CHANGES/REVISIONS TO THE PLAN, LEGIBLY, | | | INCLUDING THE REDLINED ITEMS FROM THE | | | PREVIOUS REVIEW. | | | | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|