| | PROVISO |
| | ~~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | THIS PROVISO IS BEING ISSUED TO ALLOW |
| | THE ELECTRICAL WORK TO BEGIN WITHOUT |
| | DELAY. THERE ARE THE FOLLOWING ISSUES |
| | HOWEVER,THAT NEED TO BE ADDRESSED PRIOR |
| | TO ROUGH INSPECTION. |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW AS A REVISION TO THIS PERMIT. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 3} PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5. SUBMIT COUNTER LOCA |
| | TION PLAN ON THE DRAWING TO BE REVIEWED |
| | FOR COMPLIANCE. SEE 210.8(A)(6) ALSO. |
| | |
| | 4} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 5} PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12`. SEE REDLINED PLANS, |
| | REDRAW PER ACTUAL LOCATIONS. |
| | |
| | 6} SEE NFPA-72, 1999 EDITION FOR SMOKE D |
| | ETECTOR LOCATION. (3' FROM BATH DOORS). |
| | |
| | 7} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |