| 2004-04-23 00:00:00 | BUILDING REVIEW PROVISO: |
| | 1-PROVIDE COMPLETE PRODUCT APPROVAL |
| | ASSEMBLY FOR FRENCH DOORS W/ SIDELITES |
| | AND TRANSOM ABOVE ASSEMBLY AS SHOWN ON |
| | PLANS. SPECIFY ALL FASTENERS INCLUDING |
| | ATTACHMENT OF MULLION TO WALL AND DOOR |
| | AND WINDOW ATTACHMENT TO MULLION. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 2-PROVIDE COMPLETE DETAIL FOR STRUCTURAL |
| | FACIA AT REAR PORCH. SPECIFY ALL |
| | FASTENERS. SEC. 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE COMPLETE DETAIL SHOWING |
| | INSTALLATION OF (2)B1 CONNECTORS AT |
| | THE ENDS OF GIRDER TRUSSES AT ENTRY |
| | PORCH. SECTION 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL |
| | FOR ENTRY DOORS WITH IMPACT GLAZING AS |
| | CALLED FOR IN SHEET A1. |
| | 5-PROVIDE COMPLETE KNEE WALL SECTION/DET |
| | AT ENTRY PORCH. SEE ROOF FRAMING PLAN |
| | AND PROVIDE ALSO A DETAIL SHOWING HOW |
| | IS 2X4 KNEE WALL ATTACHED TO TRUSSES |
| | BELOW IF TRUSSES RUN PARALLEL TO THE |
| | KNEE WALL. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 6-IF STORM SHUTTERS ARE TO BE INSTALLED |
| | IN THIS HOUSE, THEN PROVIDE COMPLETE |
| | INFORMATION UNDER A SEPARATE PERMIT. |