| 2004-03-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-PROVIDE STRUCTURAL BUCK DETAIL @ ENTRY |
| | DOORS SHOWING SIZE OF BUCK REQUIRED TO |
| | CLOSE GAP ACCORDING TO MASONRY OPENING |
| | SHOWN. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 3-ENERGY CALCULATIONS: A)REVISE OPENINGS |
| | CARDINAL ORIENTATION TO MATCH PLANS. |
| | B)REVISE OVERHEAD HEIGHT AND LENGTH TO |
| | MATCH PLANS. |
| | |
| | 4-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A)ALL STRUCTURAL CONNECTORS. |
| | B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. |
| | C) ENTRY DOORS. |
| | |
| | 5-CLARIFY IF USING MISSILE IMPACT GLASS |
| | OR SHUTTERS. PROVIDE COMPLETE INFO. |
| | FOR EITHER OPTION. |
| | 6-PROVIDE COMPLETE DETAIL FOR ENTRY AND |
| | REAR CONCRETE PAD FOOTING SHOWING PAD |
| | EMBEDMENT IN REFERENCE TO GRADE LEVEL. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 7-SPECIFY FASTENERS FOR 2X4 BLOCKING AT |
| | ARCHED & OVAL OPENINGS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 8-PROVIDE COMPLETE KNEE WALL DETAIL AT |
| | ENTRY PORCH. SPECIFY ALL FASTENERS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 9-SPECIFY 7/8" MIN. STUCCO THICKNESS AT |
| | FRAMED WALL AS REQUIRED BY ASTM C-926. |
| | 10-SPECIFY SAFETY GLASS IN MASTER BATH |
| | WINDOW (IF NOT USING IMPACT GLASS). |
| | 11-CAP ON DETAIL F/6 FOR STEEL COLUMN @ |
| | ENTRY PORCH DOESN'T WORK. PROVIDE |
| | DETAIL THAT SHOWS CORRECT CAP. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 12-SPECIFY CONNECTORS FOR BEAMS AT ENTRY |
| | PORCH THAT ARE RESTING ON MASONRY WALL |
| | SEE PLANS FOR COMMENTS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 13-PROVIDE COMPLETE DETAIL WITH SPECS |
| | TRUSSES AT REAR PORCH SHOWING HOW ARE |
| | THEY SUPPORTED IF THERE IS NOT A BEAM? |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 14-SHEET A3: LIVE LOAD IN ATTIC IS |
| | MEASURED IN PSF NOT PSI. REVISE NOTE |
| | AS REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |