| Plan Review Notes For Permit 04020827 |
| Permit Number |
04020827 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-04-21 00:00:00 | REDLINED PLANS, | | | REVISE BEFORE ROUGH. | | | | | | EQUIPMENT GRNDS ARE MISSING BETWEEN MAIN | | | -S AND PANELS. 250.110, 250.122 | | | | | | PLEASE SEE KW HAS NOW BEEN CHANGED TO | | | 10KW, HOWEVER, OCP WAS NOT INCREASED | | | PER 424.3B | | | | | | PLEASE SEE 250.66 FOR #2 MIN GEC FOR | | | 300A SERVICE. BASED ON MIN SEC'S IN | | | 310.15B6 | | | PLEASE ADJUST. | | | | | | PLEASE SUBMIT REVISED PLANS BEFORE ROUGH |
|