| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SEE THAT A #2 EQUIPMENT |
| | GROUND |
| | IS SHOWN BEING RAN WITH THE FEEDERS TO |
| | THE PANELS FROMTHE DISCONNECTS.VERIFY |
| | THE SIZE OF SAME. A # 6 IS REQUIRED PER |
| | 250.122. |
| | |
| | 2} THE #2 EQUIPMENT GROUND RUNNING |
| | BETWEEN DISCONNECTS IS IN VIOLATION OF |
| | 250.6(B) AND MUST NOT BE INSTALLED. |
| | |
| | 3} THE LAUNDRY CIRCUIT MUST BE |
| | CALCULATED AT 1500 VA PER 220.16(B) |
| | |
| | 4} THERE IS A POOL PUMP SHOWN ON THE |
| | DRAWINGS BUT NONE LISTED IN THE |
| | CALCULATIONS.ALSO IF THE POOL IS TO BE |
| | HEATED PLEASE SHOW THAT CALCULATION. |
| | |
| | 5} AIR HANDLER #2 IS SHOWN ON THE |
| | CALCULATIONS @ 7.5 KW AND LISTED ON THE |
| | MECHANICAL PLANS AS 10KW. PLEASE |
| | CORRELATE. |
| | |
| | 6} THE LOAD CALCULATIONS MUST CONTAIN A |
| | CALCULATION FOR THE DRYER PER 220.18. |
| | |
| | 7} PLEASE ADD A RECEPTACLE AT THE FRONT |
| | OF THE HOUSE PER 220.52(E). |
| | |
| | 8} PLEASE SHOW THE RECEPTACLE LOCATION |
| | FOR THE "WHIRL-TUB" AND SHOW GFI |
| | COMPLIANCE PER 680.62(A). |
| | |
| | 9} RECEPTACLES NEED TO BE ADDED |
| | TO BEDROOMS #3 & #4 TO COMPLY WITH |
| | 210.52(A)(2). |
| | |
| | ONE SET OF REVIEWED PLANS ARE MARKED TO |
| | INDICATE THE AREAS OF COMMENTS.PLEASE |
| | SEE THIS SET AND CALL IF THERE ARE ANY |
| | QUESTIONS. |
| | |