| Plan Review Notes For Permit 04020804 |
| Permit Number |
04020804 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-24 00:00:00 | 1) THE PLANS DISPLAY AN OCCUPANT | | | LOAD OF 412 PERSONS. A FIRE ALARM | | | SYSTEM IS REQUIRED SINCE THE OCCUPANT | | | LOAD IS GREATER THAN 300 PERSONS. RE: | | | NFPA 101, THE LIFE SAFETY CODE, SECTION | | | 13.3.4.1. PLEASE ANNOTE THE PLANS | | | AS REQUIRED. | | | | | | 2) STAIR 104 SHOULD BE BUILT AT 4,7,& | | | 11. THE RISERS ARE SHOWN AT 7 1/4 | | | INCHES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|