Plan Review Notes
Plan Review Notes For Permit 04020747
Permit Number 04020747
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-23 00:00:00DENIED
  
 1) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE FBC TABLE 1604.1.
  
 2) THE COFFERED CEILING AREA IS NOT
 INCLUDED IN THE ATTIC AREA LISTED IN THE
 ENERGY CALCS. AS REQUIRED BY FBC CHAPTER
 13. PLEASE REVISE. ENERGY CALCS. ARE
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT
  
 3) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL ON A4 TO STATE THAT THEY ARE
 FASTENED THROUGH THE BUCK AND NOT TO THE
 BUCK. SEE FBC 1707.4.4.2.
  
 4) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS INSULATED OR SOLID CORE AS REQUIRED
 BY FBC CHAPTER 13 SECTION 603.
  
 5) THE MASONRY OPENING HEIGHTS LISTED
 FOR WINDOWS (12) & (13) ON THE LEFT
 ELEVATION ON A4 ARE INCORRECT (SHOULD BE
 64"). PLEASE CORRECT.
  
 6) UPDATE THE SEMCO TRUSS CONNECTOR
 SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT
 ANCHOR WITH STATE OR LOCAL APPROVAL.
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE 16'
 LONG MULLION BETWEEN THE SLIDING GLASS
 DOOR AND THE TRANSOM AT THE GREAT ROOM.
 THE ONE SUBMITTED ONLY LISTS UP TO A 12'
 MULL LENGTH.
  
 9) SUBMIT PRODUCT APPROVALS FOR THE
 CASEMENT WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714