Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop B
Sequence Number 8
Notes
Date Text
2005-06-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL AND STRUCTURAL REVISION
 SUBMITTED 4/25/05
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2SHEET A-2.2 SHOWS THE
 REVISED LAYOUT THE STAIR #9 WALKWAY AND
 THE CORRIDOR BETWEEN STAIR #2 AND #4.
 SHEETS A-1.1, A-2.7A, A-2.8, A-4.6,
 A-6.2 AND S1-2A HAVE NOT BEEN AMENDED TO
 REFLECT THE NEW LAYOUT.SUBMIT REVISED
 SHEETS.
  
 REMAINDER OF ARCHITECTURAL AND
 STRUCTURAL SHEETS HAVE BEEN
 REVIEWED/STAMPED AND ONE COPY RETAINED
 FOR CITY RECORDS.
  
 NOTE:
 THE FOLLOWING NON-COMPLIANCE HAS BEEN
 ACCEPTED IN ACCORDANCE WITH THE RULING
 OF CONSTRUCTION BOARD OF APPEALS ORDER
 (CASE# 1253):
 FBC 1003.2.5ON SHEET A-6.1 (STAIR
 NO.1 SECTION) AND SHEET A-6.2 (STAIR
 NO.2 SECTION) THE HEADROOM IS SHOWN, AS
 AN "EXISTING CONDITION", AT 6 FT 6-1/2
 INCHES AND 6 FT 6 INCHES RESPECTIVELY.
 THE REQUIREMENT OF THE CODE APPLICABLE
 TO THE CURRENT PROJECT IS 6 FT 8
 INCHES.ACCEPTED IN ACCORDANCE WITH
 CBAA CASE# 1253