| Date |
Text |
| 2005-01-03 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | SUBMITTAL ON 12/28/04 FOR R.C. ALUMINUM |
| | DOOR AND WINDOW PACKAGE. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) THE PERMIT WAS ISSUED WITH THE |
| | FOLLOWING PROVISO: |
| | |
| | "INSUFFICIENT PRODUCT APPROVAL INFO: |
| | AS REQUESTED IN VILLA LOFTS' LETTER |
| | DATED APRIL 26, 2004, THE FIXED GLASS |
| | WINDOWS, HORIZONTAL SLIDING WINDOWS |
| | AND FRENCH DOORS SHALL BE UNDER A |
| | SEPARATE PERMIT WITH FEES BASED ON A |
| | MINIMUM VALUE OF $104,308.75" |
| | |
| | THIS CONDITION HAS NOT BEEN MET.THIS |
| | R.C. ALUMINUM PACKAGE WAS BROUGHT IN, |
| | ON |
| | 12/28/04, AS A 'NO FEE SUBMITTAL'. |
| | RESUBMIT AS A SEPARATE PERMIT |
| | APPLICATION.THE FEE CALCULATION WILL |
| | BE BASED ON THE VALUE OF THE CONTRACT |
| | FOR THE R.C. ALUMINUM DOOR AND WINDOW |
| | PACKAGE |
| | |
| | 2) A FULL REVIEW HAS NOT BEEN CARRIED |
| | OUT (SEE COMMENT 1, ABOVE).THE |
| | FOLLOWING INITIAL OBSERVATIONS ARE MADE |
| | ONLY TO EXPEDITE THE PROCESS.A FULL |
| | REVIEW WILL BE CARRIED OUT WHEN THE |
| | REQUIRED PERMIT APPLICATION IS |
| | RECEIVED. |
| | |
| | 3) FBC* 101.4.2APPROPRIATE BUILDING |
| | CODE.R.C. ALUMINUM INDUSTRIES |
| | CALCULATION SHEET DC-1 CITES SOUTH |
| | FLORIDA BUILDING CODE 2004 FOR DESIGN. |
| | THE APPLICABLE CODE IS FLORIDA BUILDING |
| | CODE 2001 (WITH 2002 AND 2003 |
| | AMENDMENTS).AMEND THE CALCULATIONS. |
| | |
| | 4) SUBMITTED PRODUCT APPROVALS. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | (IF YOU FIND THAT THE QUOTED WEB PAGE |
| | IS |
| | NO LONGER AVAILABLE, PLEASE INFORM THE |
| | PLAN REVIEWER) |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL |
| | INFO |
| | TELEPHONE: (561) 805 6716ROBERT |
| | BROWN |
| | E-MAIL: [email protected] |