| Plan Review Notes For Permit 04020684 |
| Permit Number |
04020684 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-08-26 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | A. FROM PREVIOUS REVISION REVIEW: | | | 4. SHT P-12 INDICATE THE TOTAL SQUARE | | | FEET DRAINING INTO THE EXISTING 6" STORM | | | LINE INCLUDING THE 2880 SF FROM RWL #2, | | | AND ON THE OTHER STORM LINE INCLUDING | | | THE 1310 SF FROM RWL #6. TABLE 1106.3 | | | ***************NEW COMMENT************** | | | 1B. GAS RISER DIAGRAM WAS NOT INCLUDED | | | IN THE ORIGINAL PLANS. GAS PLANS WERE | | | SUBMITTED BY THE PLUMBING CONTRACTOR AND | | | WERE APPROVED. GAS PERMIT WAS ISSUED ON | | | THE GAS RISER DIAGRAM PROVIDED AND DOES | | | NOT REFLECT THE GAS RISER SUBMITTED IN | | | THIS REVISION. PLEASE COORDINATE WITH | | | THE PLUMBING CONTRACTOR AND INDICATE | | | WHICH SYSTEM WILL BE USED, AND IF A | | | REVISION WILL BE SUBMITTED, IT WILL BE | | | SUBMITTED UNDER THE GAS PERMIT | | | (05031733). | | | 2B. INFORMATIONAL: SHT P-10.0 HAS BEEN | | | APPROVED, BUT AS INDICATED IN PRIOR | | | REVISION, RISERS S/2B & S/3 SHALL BE | | | REVISED TO REFLECT THE CHANGES SHOWN ON | | | SHEET P-4.A. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|