2004-12-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 REVISION SUBMITTED 11/15/03
  
 1) FBC 1003.2.5ON SHEET A-6.1 (STAIR
 NO.1 SECTION) AND SHEET A-6.2 (STAIR
 NO.2 SECTION) THE HEADROOM IS SHOWN, AS
 AN "EXISTING CONDITION", AT 6 FT 6-1/2
 INCHES AND 6 FT 6 INCHES RESPECTIVELY.
 THE REQUIREMENT OF THE CODE APPLICABLE
 TO THE CURRENT PROJECT IS 6 FT 8
 INCHES.
 AMEND THE PLAN TO SHOW HOW THIS WILL BE
 ACHIEVED.IT IS NOTED THAT THIS IS AN
 EXISTING CONDITION BUT CURRENT CODE
 REQUIREMENTS FOR MEANS OF EGRESS MUST
 BE
 MET.
  
 2) FBC* 104.2.1.3SHEET S6-3 HAS ONE
 CLOUDED REVISION BUT THERE IS NO
 REVISION MARKER AND REVISION HISTORY
 HAS
 BEEN OMITTED FROM THE TITLE BLOCK.
 ALSO
 THE ADDITION OF DETAIL 14 HAS NOT BEEN
 FLAGGED.
  
 3) SHEET PT-1 THROUGH PT-4, THE
 POST-TENSION SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD BEFORE SUBMITTAL.ALSO THE
 TITLE
 BLOCK SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION (ENGINEERING BUSINESS)
 NUMBER (EB 9829) FOR NEWTONIAN SOLUTIONS
 INC.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN