| 2004-12-07 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | REVISION SUBMITTED 11/15/03 |
| | |
| | 1) FBC 1003.2.5ON SHEET A-6.1 (STAIR |
| | NO.1 SECTION) AND SHEET A-6.2 (STAIR |
| | NO.2 SECTION) THE HEADROOM IS SHOWN, AS |
| | AN "EXISTING CONDITION", AT 6 FT 6-1/2 |
| | INCHES AND 6 FT 6 INCHES RESPECTIVELY. |
| | THE REQUIREMENT OF THE CODE APPLICABLE |
| | TO THE CURRENT PROJECT IS 6 FT 8 |
| | INCHES. |
| | AMEND THE PLAN TO SHOW HOW THIS WILL BE |
| | ACHIEVED.IT IS NOTED THAT THIS IS AN |
| | EXISTING CONDITION BUT CURRENT CODE |
| | REQUIREMENTS FOR MEANS OF EGRESS MUST |
| | BE |
| | MET. |
| | |
| | 2) FBC* 104.2.1.3SHEET S6-3 HAS ONE |
| | CLOUDED REVISION BUT THERE IS NO |
| | REVISION MARKER AND REVISION HISTORY |
| | HAS |
| | BEEN OMITTED FROM THE TITLE BLOCK. |
| | ALSO |
| | THE ADDITION OF DETAIL 14 HAS NOT BEEN |
| | FLAGGED. |
| | |
| | 3) SHEET PT-1 THROUGH PT-4, THE |
| | POST-TENSION SHOP DRAWINGS SHALL BE |
| | REVIEWED AND STAMPED BY THE ENGINEER OF |
| | RECORD BEFORE SUBMITTAL.ALSO THE |
| | TITLE |
| | BLOCK SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION (ENGINEERING BUSINESS) |
| | NUMBER (EB 9829) FOR NEWTONIAN SOLUTIONS |
| | INC. |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |