Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop P
Sequence Number 5
Notes
Date Text
2005-07-20 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-1 REVISION #7 INDICATE RWL
 NUMBER OF STORM LINE CONNECTING BETWEEN
 PARKING SPACES 26 & 27. - NO REVISION #8
 FOUND. PLEASE CLARIFY. SECTION 104.2.1.
 2. SHT P-2 SEE PROVISO FROM REVISION
 DATE STAMPED JUNE 13, 2005. SHOW THE
 LOCATION OF SECONDARY ROOF DRAINS.
 SECTION 1107.
 3. SHT P-4A WHITE OUT IS NOT APPROVED
 FOR PLAN CORRECTIONS/CHANGES. SECTION
 104.2.1.3.
 4. P-12 INDICATE THE TOTAL SQUARE FEET
 DRAINING INTO THE EXISTING 6" STORM LINE
 INCLUDING THE 2880 SF FROM RWL #2, AND
 ON THE OTHER STORM LINE INCLUDING THE
 1310 SF FROM RWL #6. TABLE 1106.3
 5. RECALCULATE THE SQUARE FEET FOR THE
 STORM DRAIN LINE FOR RWL #4. CHECK ALL
 PIPE SIZES PER TABLE 1106.3.
 6. THE SANITARY RISER DIAGRAMS S/2B AND
 S/3 SHALL BE REVISED TO REFLECT THE
 CHANGES SHOWN ON SHEET P-4.A. SECTION
 104.2.1.
 7. INFORMATIONAL - THE FOLLOWING SHEETS
 HAVE BEEN APPROVED AS REVISIONS, AND ONE
 SET HAS BEEN RETAINED FOR THE FILE SET.
 P-3, P-4.A, P-8 AND P-13.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]