| 2005-07-22 00:00:00 | DENIED: |
| | PLEASE NOTE, COMMENTS FROM REVIEW DATED |
| | 6/15/05 WERE NOT ADDRESSED.PAGES |
| | SUBMITTED FOR REVISION ON 6-22-05 ARE AS |
| | FOLLOWS; AC-1, AC-2, AC-3, AC-4, AC-4A. |
| | |
| | 1.PLAN SHEET AC-2 - EXIT CORRIDOR |
| | INDICATES SPF-3,PLEASE CLARIFY, WILL |
| | THIS ONLY RUN DURING EMERGENCY POWER? |
| | PLEASE NOTE, SPF-3 IS NOT INDICATED ON |
| | THE EQUIPMENT SCHEDULE ON PLAN SHEET |
| | AC-8.0 OR LISTED WITH THE STAIRWELL |
| | PRESSURIZATION EQUIPMENT LISTED ON PLAN |
| | SHEET AC-11. |
| | |
| | 2.PLAN SHEET AC-3, AC-4 & AC-4A DO NOT |
| | INDICATE LOCATION OF LEF-1.PLANS SHOW |
| | LEF-1 HAS BEEN DELETED BUT IS STILL |
| | INDICATED IN THE SEQUENCE OF OPERATION |
| | ON PLAN SHEET AC-11 (THIS SHEET HAS NOT |
| | BEEN REVISED).PLEASE INDICATE MEDTHOD |
| | OF SMOKE CONTROL LISTED UNDER 2001 FBC |
| | 412.5. |
| | |
| | PLEASE NOTE, MECHANICAL REVISIONS |
| | SUBMITTED 6-2-05 WERE DENIED AND |
| | COMMENTS WERE NOT ADDRESSED.REVISIONS |
| | SUBMITTED UNDER THIS REVIEW CONTAIN THE |
| | SAME COMMENTS TO PROPOSED REVISIONS. |
| | PLEASE PROVIDE A RESPONSE LETTER TO |
| | COMMENTS. |
| | |