Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop M
Sequence Number 5
Notes
Date Text
2005-07-22 00:00:00DENIED:
 PLEASE NOTE, COMMENTS FROM REVIEW DATED
 6/15/05 WERE NOT ADDRESSED.PAGES
 SUBMITTED FOR REVISION ON 6-22-05 ARE AS
 FOLLOWS; AC-1, AC-2, AC-3, AC-4, AC-4A.
  
 1.PLAN SHEET AC-2 - EXIT CORRIDOR
 INDICATES SPF-3,PLEASE CLARIFY, WILL
 THIS ONLY RUN DURING EMERGENCY POWER?
 PLEASE NOTE, SPF-3 IS NOT INDICATED ON
 THE EQUIPMENT SCHEDULE ON PLAN SHEET
 AC-8.0 OR LISTED WITH THE STAIRWELL
 PRESSURIZATION EQUIPMENT LISTED ON PLAN
 SHEET AC-11.
  
 2.PLAN SHEET AC-3, AC-4 & AC-4A DO NOT
 INDICATE LOCATION OF LEF-1.PLANS SHOW
 LEF-1 HAS BEEN DELETED BUT IS STILL
 INDICATED IN THE SEQUENCE OF OPERATION
 ON PLAN SHEET AC-11 (THIS SHEET HAS NOT
 BEEN REVISED).PLEASE INDICATE MEDTHOD
 OF SMOKE CONTROL LISTED UNDER 2001 FBC
 412.5.
  
 PLEASE NOTE, MECHANICAL REVISIONS
 SUBMITTED 6-2-05 WERE DENIED AND
 COMMENTS WERE NOT ADDRESSED.REVISIONS
 SUBMITTED UNDER THIS REVIEW CONTAIN THE
 SAME COMMENTS TO PROPOSED REVISIONS.
 PLEASE PROVIDE A RESPONSE LETTER TO
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.