Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop E
Sequence Number 5
Notes
Date Text
2005-07-18 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM CONDUITS ON
 RISER DIAGRAM. PLEASE SEE SOME OF THESE
 WERE NOTED ON PREVIOUS REVIEW.
 MAIN 1 TO TAP BOX? ETC,
 250.110,250.24,250.122
  
 2)NOTE: PLEASE SEE APARTMENT PANEL "C",
 WHICH APPEARS TO SHOW DRYER AND WASHER
 AS "SPARE"? PLEASE SEE NEC
 210.52F,210.11C2 WHICH REQUIRES A MIN OF
 ONE LAUNDRY RM CIRCUIT/WASHER FOR A
 DWELLING.
  
 3)NOTE: PLEASE SEE PREVIOUS REQUESTED
 FIRE PUMP/ FIRE PUMP CONTROLLER,
 GENERATOR, AND ATS TO BE PERMITTED. THIS
 WAS GIVEN ON PROVISO AND THIS MUST BE
 ADDRESSED BEFORE REVISIONS WILL BE
 STAMPED.
  
 4)NOTE: PLEASE SEE REVISED ELECTRICAL
 ROOMS, ELEVATOR MACHINE RM IS NOW NOT ON
 PLANS??
 PLEASE CLARIFY?
 620.23,620.24
  
 5)NOTE: PLEASE SEE 445.13 FOR AMPACITY
 OF CONDUCTORS FOR GENERATOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-07-15 00:00:00PLANS IN ELECTRICAL FOR REVIEW.