| Plan Review Notes For Permit 04020684 |
| Permit Number |
04020684 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-06-13 00:00:00 | REVISION DENIED | | | | | | 1. SHT P10 FROM PREVIOUS REVIEW. SANT. | | | RISERS S/1A-S/7 & S/1C/CU. FIXTURE UNITS | | | ADDED TO STACKS SHALL BE 16 NOT 10. 5FU | | | FOR BATHROOM GROUP, AND 1FU FOR LAV AND | | | 2FU FOR ADDED TUB OR SHOWER. - SHOW | | | CORRECT FIXTURE UNITS FOR STACKS. - ONE | | | SHT P10 IS A COPY OF THE SIGNED, SEALED, | | | DATED SHEET. ALL SETS SHALL BE SIGNED, | | | SEALED & DATED. FAC 61G15-23.002 | | | | | | 2. SHT P12 ALL CORRECTIONS HAVE BEEN | | | ADDRESSED FROM LAST REVISION REVIEW, BUT | | | A NEW COMMENT WAS DISCOVERED. THE 6" | | | PIPE AT 5490 SF IS NOT LARGE ENOUGH. | | | MINIMUM 8" PIPE IS REQUIRED. TABLE | | | 1106.3. | | | | | | 3. ALL OTHER SHEETS HAVE BEEN APPROVED | | | AND ONE SET HAS THEM REMOVED FOR FILE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|