Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop P
Sequence Number 4
Notes
Date Text
2005-06-13 00:00:00REVISION DENIED
  
 1. SHT P10 FROM PREVIOUS REVIEW. SANT.
 RISERS S/1A-S/7 & S/1C/CU. FIXTURE UNITS
 ADDED TO STACKS SHALL BE 16 NOT 10. 5FU
 FOR BATHROOM GROUP, AND 1FU FOR LAV AND
 2FU FOR ADDED TUB OR SHOWER. - SHOW
 CORRECT FIXTURE UNITS FOR STACKS. - ONE
 SHT P10 IS A COPY OF THE SIGNED, SEALED,
 DATED SHEET. ALL SETS SHALL BE SIGNED,
 SEALED & DATED. FAC 61G15-23.002
  
 2. SHT P12 ALL CORRECTIONS HAVE BEEN
 ADDRESSED FROM LAST REVISION REVIEW, BUT
 A NEW COMMENT WAS DISCOVERED. THE 6"
 PIPE AT 5490 SF IS NOT LARGE ENOUGH.
 MINIMUM 8" PIPE IS REQUIRED. TABLE
 1106.3.
  
 3. ALL OTHER SHEETS HAVE BEEN APPROVED
 AND ONE SET HAS THEM REMOVED FOR FILE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]