2005-06-15 00:00:00DENIED:
 1.PLAN SHEET AC-2 INDICATES SPF-4
 BEING DELETED.HOW WILL VENTILATION
 REQUIREMENT BE MET INACCORDANCE WITH
 2001 FBC(M)TABLE 403.3.PLEASE ALSO
 CLARIFY RATING OF THIS AREA AS WELL AS
 HALL SERVICED BY SPF-3.ARE THESE EXIT
 CORRIDORS?
  
 2.PLAN SHEET AC-3 THROUGH AC-6
 INDICATES THE REMOVAL OF LEF-1.PLAN
 SHEET AC-11 SEQUENCE OF OPERATION NOW
 READS "RTU-1 WILL SHUT DOWN".PLEASE
 CLARIFY HOW THE REQUIREMENTS OF 412.5
 WILL BE MET.
  
 3.PLAN SHEET AC-11 THE SEQUENCE OF
 OPERATION FOR FLOORS 2 THROUGH 12, STILL
 INDICATES LEF-1 AS A PART OF THE SMOKE
 CONTROL SYSTEM BUT ARE REMOVED FROM THE
 PLAN SHEETS (AC-3 THRU AC-6).
  