Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop E
Sequence Number 4
Notes
Date Text
2005-05-17 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE "PROVISO" GIVEN ON
 4/18/04.
 PLEASE SEE NO FURTHER ELECTRICAL
 REVISIONS SHALL BE STAMPED FOR REVIEW
 UNTIL FIRE PUMP/FIRE PUMP CONTROLLER,
 GENERATOR/ATS ETC IS APPLIED FOR FOR
 PERMIT.
 THIS WAS REQUESTED OVER 1YR AGO.
  
 2)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS SHOWN FROM FPL/METER TO THE
 FIRST MEANS OF DISCONNETC. (FIRE PUMP )?
 PLEASE SEE SOME CONDUITS ON RISER ARE
 MISSING EQUIPMENT GROUNDING CONDUCTORS.
 250.24,250.110, SIZED PER 250.122
  
  
 NOTES FOR SIGNAGE AND MAPPING ADDED ON
 PLANS.
 MCB WAS ADDED TO EDP.
  
 PLEASER BE SURE TO SUBMIT INFORMATION
 FOR PERMIT BEFORE FURTHER REVISIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717