| Plan Review Notes For Permit 04020684 |
| Permit Number |
04020684 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-12-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P-1 CONDENSATE SHALL DRAIN | | | SEPARATELY FROM THE BUILDING AND THEN | | | CONNECT TO STORM DRAIN, OR A CATCH | | | BASIN | | | A RELIEF VENT IS REQUIRED AS CONDENSATE | | | EXITS THE BUILDING. | | | 2) SHT P-10 INDICATES REVISION #1, BUT | | | THE REVISIONS ARE NUMBERED #2. PLEASE | | | CLARIFY. SECTION 104.2.1 | | | 3) SHT P-10 SANT RISERS 5/1A-S/7, AND | | | S1C/S7. FIXTURE UNITS ADDED TO STACK | | | SHALL BE 16 NOT 10. 5 FU FOR BATHROOM | | | GROUP, A 1 FU FOR LAV, AND 2 FOR ADDED | | | TUB OR SHOWER. | | | 4) SHT P-11 CONDENSATE RISERS C/1A, C/2, | | | AND C/2A APPEAR TO HAVE BEEN CAPPED OFF. | | | THESE RISERS SHALL VENT THROUGH THE ROOF | | | AND SHALL NOT BE CAPPED OFF. PLEASE | | | CLARIFY. SECTION 104.2.1 | | | 5) SHT P-12 RWL/2 AND RWL/6 COMBINED | | | TOTAL UP TO 3500 SF. MAXIMUM SF ON 5" | | | STORM HORIZONTAL DRAINAGE PIPE IS 2969 | | | SF ON 5" PIPE. TABLE 1106.3 | | | 6) FOLLOWING SHEETS WERE OK AND WILL BE | | | STAMPED WHEN RESUBMITTED. P-2, P-3, P-4, | | | P-5, P-5.1, P-7, P-8, P-9, P-10.1, AND | | | P-13. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|