Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop P
Sequence Number 3
Notes
Date Text
2004-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-1 CONDENSATE SHALL DRAIN
 SEPARATELY FROM THE BUILDING AND THEN
 CONNECT TO STORM DRAIN, OR A CATCH
 BASIN
 A RELIEF VENT IS REQUIRED AS CONDENSATE
 EXITS THE BUILDING.
 2) SHT P-10 INDICATES REVISION #1, BUT
 THE REVISIONS ARE NUMBERED #2. PLEASE
 CLARIFY. SECTION 104.2.1
 3) SHT P-10 SANT RISERS 5/1A-S/7, AND
 S1C/S7. FIXTURE UNITS ADDED TO STACK
 SHALL BE 16 NOT 10. 5 FU FOR BATHROOM
 GROUP, A 1 FU FOR LAV, AND 2 FOR ADDED
 TUB OR SHOWER.
 4) SHT P-11 CONDENSATE RISERS C/1A, C/2,
 AND C/2A APPEAR TO HAVE BEEN CAPPED OFF.
 THESE RISERS SHALL VENT THROUGH THE ROOF
 AND SHALL NOT BE CAPPED OFF. PLEASE
 CLARIFY. SECTION 104.2.1
 5) SHT P-12 RWL/2 AND RWL/6 COMBINED
 TOTAL UP TO 3500 SF. MAXIMUM SF ON 5"
 STORM HORIZONTAL DRAINAGE PIPE IS 2969
 SF ON 5" PIPE. TABLE 1106.3
 6) FOLLOWING SHEETS WERE OK AND WILL BE
 STAMPED WHEN RESUBMITTED. P-2, P-3, P-4,
 P-5, P-5.1, P-7, P-8, P-9, P-10.1, AND
 P-13.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]