| Date |
Text |
| 2004-04-22 00:00:00 | 1) THE ALTERNATIVE EGRESS FROM THE 2ND |
| | FLOOR COMMON AREA THAT IS PROVIDED |
| | THROUGH THE EXISTING TOWER SHALL BE |
| | WIDE ENOUGH TO ACCEPT THE |
| | ANTICIPATED LOAD. |
| | |
| | 2) NO STORAGE IS PERMITTED IN ANY |
| | IDENTIFIED VOID AREAS DESIGNATED |
| | ON THE PLANS. IF STORAGE IS PLANNED, |
| | THE FIRE SPRINKLER PROTECTION IS |
| | REQUIRED. |
| | |
| | 3) OAK TREES PLANNED CANNOT INTERFERE |
| | WITH ANY FIRE LANES. |
| | |
| | 4) THE MIAMI STANDARD1 1/2 THREAD |
| | NOTE IS NOT APPLICABLE TO THE CITY |
| | OF WEST PALM BEACH. PAGE FP-7. |
| | |
| | 5) ROOF PLAN PAGE FP-5 INDICATES |
| | FDC'S. THESE SHOULD BE CALLED ROOF |
| | MANIFOLDS. |
| | |
| | 6) PRODUCT DATA WILL BE REQUIRED FOR |
| | THE FIRE PUMP AND EMERGENCY |
| | GENERATOR. SEPARATE PLANS AND PERMITS |
| | REQUIRED. |
| | |
| | 7) SINCE EOL'S ARE SHOWN, THE FIRE |
| | ALARM SYSTEM SHALL BE FULLY |
| | ADDRESSABLE. |
| | |
| | 8) SMOKE DETECTORS IN UNITS B & C APPEAR |
| | TO BE INSTALLED TOO CLOSE TOGETHER. |
| | PLEASE REVISE. |
| | |
| | 9) EXIT SIGNS NEEDED NEAR GARAGE DOUBLE |
| | DOOR EXIT TUNNEL. PLEASE PROVIDE. |
| | |
| | 10) PLEASE SEE ELECTRICAL PLAN |
| | REVIEWER NOTES. |
| | |
| | APPROVED PROVISO: |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |