2004-04-22 00:00:001) THE ALTERNATIVE EGRESS FROM THE 2ND
 FLOOR COMMON AREA THAT IS PROVIDED
 THROUGH THE EXISTING TOWER SHALL BE
 WIDE ENOUGH TO ACCEPT THE
 ANTICIPATED LOAD.
  
 2) NO STORAGE IS PERMITTED IN ANY
 IDENTIFIED VOID AREAS DESIGNATED
 ON THE PLANS. IF STORAGE IS PLANNED,
 THE FIRE SPRINKLER PROTECTION IS
 REQUIRED.
  
 3) OAK TREES PLANNED CANNOT INTERFERE
 WITH ANY FIRE LANES.
  
 4) THE MIAMI STANDARD1 1/2 THREAD
 NOTE IS NOT APPLICABLE TO THE CITY
 OF WEST PALM BEACH. PAGE FP-7.
  
 5) ROOF PLAN PAGE FP-5 INDICATES
 FDC'S. THESE SHOULD BE CALLED ROOF
 MANIFOLDS.
  
 6) PRODUCT DATA WILL BE REQUIRED FOR
 THE FIRE PUMP AND EMERGENCY
 GENERATOR. SEPARATE PLANS AND PERMITS
 REQUIRED.
  
 7) SINCE EOL'S ARE SHOWN, THE FIRE
 ALARM SYSTEM SHALL BE FULLY
 ADDRESSABLE.
  
 8) SMOKE DETECTORS IN UNITS B & C APPEAR
 TO BE INSTALLED TOO CLOSE TOGETHER.
 PLEASE REVISE.
  
 9) EXIT SIGNS NEEDED NEAR GARAGE DOUBLE
 DOOR EXIT TUNNEL. PLEASE PROVIDE.
  
 10) PLEASE SEE ELECTRICAL PLAN
 REVIEWER NOTES.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910