Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-18 00:00:00******* NOTES REDLINED *******
 ******* PROVISO ********
  
 1)NOTE: PLEASE PROVIDE ALL INFORMATION/
 SPECS FOR FIRE PUMP CONTROLLER/ PUMP/
 AND GENERATOR.
 PLEASE SEE FIRE REVIEW COMMENTS PERTAIN-
 ING GENERATOR SYSTEM. THIS WILL BE REQ'D
 TO BE UNDER A SEPARATE PERMIT.
 PLEASE BE SURE FIRE PUMP CONTROLLER
 MEETS 230.76,230.79 AND 110.27
 FIRE DEPT MAY NOT OPEN EQUIPMENT TO
 DISCONNECT POWER. 110.27ALL SPECS WILL
 BE REQUIRED TO BE SUBMITTED W/PERMIT
 APPLICATION IF NOT BEFORE, PENDING FIRE
 REVIEW COMMENTS.
  
 2)NOTE: NOTES REDLINED FOR ALL REQ'D
 SIGNAGE AT EACH ELECTRICAL ROOM AND FIRE
 PUMP ROOM. SIGNAGE AND A DIAGRAM WILL BE
 REQ'D AT FIRE CONTROL ROOM TO INDICATE
 AND DIRECT FIRE DEPT PERSONNEL TO ALL
 MAIN ELECTRICAL ROOMS/ GENERATOR LOCAT-
 -IONS/FIRE PUMP ROOMS.
 230.2E
  
 3)NOTE: NOTES REDLINED FOR PANIC HARD-
 -WARE REQ'D ON MAIN ELECTRICAL ROOM
 DOORS PER 110.26
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]