| 2004-04-18 00:00:00 | ******* NOTES REDLINED ******* |
| | ******* PROVISO ******** |
| | |
| | 1)NOTE: PLEASE PROVIDE ALL INFORMATION/ |
| | SPECS FOR FIRE PUMP CONTROLLER/ PUMP/ |
| | AND GENERATOR. |
| | PLEASE SEE FIRE REVIEW COMMENTS PERTAIN- |
| | ING GENERATOR SYSTEM. THIS WILL BE REQ'D |
| | TO BE UNDER A SEPARATE PERMIT. |
| | PLEASE BE SURE FIRE PUMP CONTROLLER |
| | MEETS 230.76,230.79 AND 110.27 |
| | FIRE DEPT MAY NOT OPEN EQUIPMENT TO |
| | DISCONNECT POWER. 110.27ALL SPECS WILL |
| | BE REQUIRED TO BE SUBMITTED W/PERMIT |
| | APPLICATION IF NOT BEFORE, PENDING FIRE |
| | REVIEW COMMENTS. |
| | |
| | 2)NOTE: NOTES REDLINED FOR ALL REQ'D |
| | SIGNAGE AT EACH ELECTRICAL ROOM AND FIRE |
| | PUMP ROOM. SIGNAGE AND A DIAGRAM WILL BE |
| | REQ'D AT FIRE CONTROL ROOM TO INDICATE |
| | AND DIRECT FIRE DEPT PERSONNEL TO ALL |
| | MAIN ELECTRICAL ROOMS/ GENERATOR LOCAT- |
| | -IONS/FIRE PUMP ROOMS. |
| | 230.2E |
| | |
| | 3)NOTE: NOTES REDLINED FOR PANIC HARD- |
| | -WARE REQ'D ON MAIN ELECTRICAL ROOM |
| | DOORS PER 110.26 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |