Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop P
Sequence Number 1
Notes
Date Text
2004-02-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLORIDA STATUTES
  
 1) EAST TOWER SHALL COMPLY WITH FBC-2001
 PLUMBING PER SECTION 3401.7.1.1.1
 2) CERTIFICATE OF AUTHORIZATION NUMBER
 IS REQUIRED ON ALL ARCHITECTURAL SHEETS
 PER FS 481.291.
 3) SHT A-2.1 TRENCH DRAIN AT TRASH DUMP-
 STER. IS THIS TRENCH DRAIN CONNECTED TO
 STORM? WILL THE DUMPSTER PAD BE WASHED
 DOWN INTO THE TRENCH DRAIN? PLEASE
 CLAIRFY.
 4) SHT A2.2 SUBMIT CALCULATIONS FOR
 COMMON AREAS PER TABLE 403.1. INDICATE
 AREAS TO INCLUDE CONFERENCE ROOM, MULTI-
 MEDIA, HEALTH CLUB, MANAGERS OFFICE ECT.
 5) SHT A-5.5 EMPLOYEE TOILET ROOM @ THE
 GROUND FLOOR, DOOR SHALL NOT OPEN INTO
 THE TURNING CIRCLE AND WATER CLOSET
 SHALL NOT OBSTRUCT THE TURNING CILCLE.
 SECTION 11-4.22.3.
 6) SHT A-8.2 DETAIL #4, PER SECTION
 1503.4.2 OVERFLOW SCUPPERS SHALL BE IN-
 STALLED IN WALLS OR PARAPETS WITH THE
 INLET FLOW LINE NOT LESS THAN 2" ABOVE
 THE ROOF SURFACE, EXCLUDING SUMPS, OR
 MORE THAN 4" ABOVE THE ROOF SURFACE AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL
 TO REQUIRED VERTICAL LEADERS OR DOWN-
 SPOUTS OR WALL OR PARAPET SCUPPERS.
 7) SHT P-7 WATER RISER DIAGRAMS, AIR
 CHAMBERS ARE NOT APPROVED PER SECTION
 604.9. DELETE FROM RISER DIAGRAMS.
 8) SHT P-8 SANITARY PIPING COLLECTION
 ISOMETRIC, FLOOR DRAINS IN EMPLOYEE AND
 GUEST TOILET ROOMS ARE NOT VENTED.
 CONNECT F.D.'S TO TOILET ROOM PIPING.
 SECTION 901.2.1
 9) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2
 10) SHT P-11 WATER RISER W/3, AN RPZ
 BACKFLOW IS REQUIRED ON WATER LINE TO
 TRASH CHUTE. SECTION 608.13.2
 11) SHT P-12 STORM DRAIN PIPING, RWL/2
 1620 SF - MAX 1600 SF @ 1/8" PER FT.
 EITHER INCREASE PIPE SIZE OF SHOW 1/4"
 PER FT. SLOPE ON PIPE. - RWL/3 6" SHOWS
 170 SF, BUT ADDS UP TO 1700 SF. PLEASE
 CHANGE PLANS.
 12) SHT P-10.1 IDENTIFY RISER BETWEEN
 S/4 & S/6. SHOW FU'S. - S/7 FU'S TO BE
 A TOTAL OF 16. (SHOWS 10). ADD ONE LAV
 AND TUB OR SHOWER TO EACH FLOOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]