| 2004-03-05 00:00:00 | DENIED: |
| | 1.PLEASE PROVIDE SEQUENCE OF OPERATION |
| | FOR THE SMOKE EVAC SYSTEM. |
| | |
| | 2.CORRIDORS IN THE "LOFT" AREAS APPEAR |
| | TO BE BY SMOKE CONTROL/STACK EFFECT. |
| | SHOW COMPLIANCE WITH 2001 FBC 412.5 |
| | |
| | 3.PLANS DO NOT INDICATE THE EXISTING |
| | ENCLOSED GARAGE.INDICATE ANY NEW OR |
| | EXISTING VENTILATION & EVAC SYSTEMS. |
| | SHOW COMPLIANCE WITH 2001 FBC 411.4.2. |
| | |
| | 4.PLAN SHEET AC-1, TOILET EXHAUST IS |
| | SHOWN TERMINATING IN THE ENCLOSED GARAGE |
| | EXHAUST IS TO TERMINATE TO THE OUTDOORS |
| | PER 2001 FBC(M) 501.3.PLEASE NOTE, |
| | THE WALL WHERE THE EXHAUST IS TERMATING |
| | AT IS A 4 HR FIRE RATED SEPARATION WALL. |
| | |
| | 5.PLAN SHEET AC-2, 2ND FLOOR PLAN |
| | INDICATES 2 RTU-2, SHOULD INDICATE 1 |
| | RTU-3 & 1 RTU-2. |
| | |
| | 6.PLAN SHEET AC-8.0, DRYER EXHAUST |
| | INFORMATION, SPECIFIC DRYER TO BE |
| | INSTALLED FOR FINAL INSPECTION. |
| | |
| | 7.PLAN SHEET AC-8.0 APARTMENT O.A. |
| | CALCULATIONS, PER REVISION TO THE 2001 |
| | FBC(M) 403.3 EFFECTIVE JUNE 30, 2003; |
| | VENTILATION SYSTEMS FOR OTHER THAN R-3 |
| | (ONE & TWO FAMILY DWELLINGS) SHALL BE |
| | DESIGNED TO SUPPLY THE MINIMUM OF OUT- |
| | DOOR AIR IN ACCORDANCE WITH TABLE 403.3. |
| | |
| | 8.PLAN SHEET AC-9.0 REFRIGERANT |
| | ENCLOSURE TO BE 2 HR FIRE RATED & SHAFT |
| | IS TO BE VENTILATED PER NFPA 90A 3-3.4 |
| | & ASHRAE 15-92 11.12.3 (B) RESPECTIVELY. |
| | |
| | 9.PLAN SHEET AC-9.0 DETAIL FOR THE |
| | TOILET & DRYER EXHAUST, TOILET AND FRESH |
| | AIR INSTAKES ARE TO BE PROTECTED IN |
| | ACCORDANCE WITH 2001 FBC(M) 401.6. |
| | DRYER EXHAUST SHALL BE NON-SCREENED & |
| | HAVE A BACK-DRAFT DAMPER PER 2001 FBC(M) |
| | 504.4. |
| | |
| | 10. PLEASE PROVIDE INFORMATION ON THE |
| | EMERGENCY GENERATOR; LOCATION, TYPE OF |
| | GENERATOR, NEW OR EXISTING, TERMINATION |
| | OF EXHAUST, ETC. |
| | |