2004-03-05 00:00:00DENIED:
 1.PLEASE PROVIDE SEQUENCE OF OPERATION
 FOR THE SMOKE EVAC SYSTEM.
  
 2.CORRIDORS IN THE "LOFT" AREAS APPEAR
 TO BE BY SMOKE CONTROL/STACK EFFECT.
 SHOW COMPLIANCE WITH 2001 FBC 412.5
  
 3.PLANS DO NOT INDICATE THE EXISTING
 ENCLOSED GARAGE.INDICATE ANY NEW OR
 EXISTING VENTILATION & EVAC SYSTEMS.
 SHOW COMPLIANCE WITH 2001 FBC 411.4.2.
  
 4.PLAN SHEET AC-1, TOILET EXHAUST IS
 SHOWN TERMINATING IN THE ENCLOSED GARAGE
 EXHAUST IS TO TERMINATE TO THE OUTDOORS
 PER 2001 FBC(M) 501.3.PLEASE NOTE,
 THE WALL WHERE THE EXHAUST IS TERMATING
 AT IS A 4 HR FIRE RATED SEPARATION WALL.
  
 5.PLAN SHEET AC-2, 2ND FLOOR PLAN
 INDICATES 2 RTU-2, SHOULD INDICATE 1
 RTU-3 & 1 RTU-2.
  
 6.PLAN SHEET AC-8.0, DRYER EXHAUST
 INFORMATION, SPECIFIC DRYER TO BE
 INSTALLED FOR FINAL INSPECTION.
  
 7.PLAN SHEET AC-8.0 APARTMENT O.A.
 CALCULATIONS, PER REVISION TO THE 2001
 FBC(M) 403.3 EFFECTIVE JUNE 30, 2003;
 VENTILATION SYSTEMS FOR OTHER THAN R-3
 (ONE & TWO FAMILY DWELLINGS) SHALL BE
 DESIGNED TO SUPPLY THE MINIMUM OF OUT-
 DOOR AIR IN ACCORDANCE WITH TABLE 403.3.
  
 8.PLAN SHEET AC-9.0 REFRIGERANT
 ENCLOSURE TO BE 2 HR FIRE RATED & SHAFT
 IS TO BE VENTILATED PER NFPA 90A 3-3.4
 & ASHRAE 15-92 11.12.3 (B) RESPECTIVELY.
  
 9.PLAN SHEET AC-9.0 DETAIL FOR THE
 TOILET & DRYER EXHAUST, TOILET AND FRESH
 AIR INSTAKES ARE TO BE PROTECTED IN
 ACCORDANCE WITH 2001 FBC(M) 401.6.
 DRYER EXHAUST SHALL BE NON-SCREENED &
 HAVE A BACK-DRAFT DAMPER PER 2001 FBC(M)
 504.4.
  
 10. PLEASE PROVIDE INFORMATION ON THE
 EMERGENCY GENERATOR; LOCATION, TYPE OF
 GENERATOR, NEW OR EXISTING, TERMINATION
 OF EXHAUST, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.