| Date |
Text |
| 2004-02-18 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE |
| | REQUIRED ON THE FIRE LINE BACKFLOW |
| | DEVICE. |
| | |
| | 2) A TEMPORARY STANDPIPE SYSTEM WILL |
| | BE REQUIRED WHEN THE BUILDING REACHES |
| | THREE STORIES OR 30 FEET IN HEIGHT. |
| | |
| | 3) EGRESS STAIRS FOR THE BUILDING |
| | SHALL BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 4) ALL DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION SHALL COMPLY WITH |
| | NFPA 241. |
| | |
| | 5) A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 6) ON A RECENT VISIT, THE EXISTING |
| | PARKING GARAGE DISPLAYED POSSIBLE |
| | CODE VIOLATIONS. IT IS UNKNOWN IF |
| | THE REQUIRED VENTILATION SYSTEM FOR |
| | THE GARAGE IS WORKING. ALSO ALMOST |
| | ALL OF THE REQUIRED EXIT SIGNS WERE |
| | NOT ILLUMINATED. PLEASE ADVISE |
| | DISPOSITION OF THESE CODE VIOLATIONS. |
| | |
| | 7) A TWO HOUR FIRE SEPARATION IS |
| | REQUIRED BETWEEN THE EXISTING PARKING |
| | GARAGE AND THE NEW TOWER. |
| | |
| | 8) PLEASE INDICATE WHICH ELEVATORS |
| | WILL BE STRETCHER ACCESSIBLE. |
| | |
| | 9) NO DOOR PRESENT FOR STAIR # 1 ON |
| | PAGE A-2.3. |
| | |
| | 10) TACTILE SIGNAGE REQUIRED AT |
| | STAIRWELL DOORS. |
| | |
| | 11) ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE |
| | MARKED SHAFTWAY IN 6" HIGH LETTERS. |
| | |
| | 12) THE GROUND FLOOR LIFE SAFETY PLAN |
| | APPEARS CONFUSING. PLEASE CLARIFY. |
| | |
| | 13) THE BUILDING ADDRESS IS REQUIRED |
| | ON THE NEW BUILDING. A MINIMUM OF 6" |
| | HIGH NUMBERS ARE REQUIRED. |
| | |
| | 14) FDC'S ARE NOTED ON THE ROOF. THEY |
| | SHOULD READ ROOF MANIFOLDS. |
| | |
| | 15) PLEASE NOTE ON THE PLANS ALL |
| | REQUIRED ITEMS TO BE INSTALLED IN |
| | THE FIRE COMMAND ROOM AS PER 412 OF |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 16) THE NEW FIRE ALARM SYSTEM IS |
| | REQUIRED TO BE UL LISTED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 17) PLANS NEED TO MENTION "ANTICIPATED |
| | STACK" ON THE MECHANICAL PLANS. |
| | |
| | 18) ELEVATOR WARNING SIGNS REQUIRED. |
| | |
| | 19) PLEASE INDICATE OCCUPANT LOAD FOR |
| | POOL DECK. |
| | |
| | 20) ALL NEW STAIRS AND RAMPS SHAL HAVE |
| | HANDRAILS ON BOTH SIDES. |
| | |
| | 21) PLEASE PROVIDE DETAILS ON SOUND |
| | ATTENUATION INSULATION FOR TRASH |
| | CHUTE. |
| | |
| | 22) PLEASE DEMONSTRATE THAT GUARDRAILS |
| | ON STAIRS WILL RESIST A 4" SPHERE. |
| | |
| | 23) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEM INSTALLATION. |
| | |
| | 24) PLEASE EXPLAIN NOTE # 7 ON A-5.2. |
| | HOW WILL FIRE RESCUE GAIN ACCESS TO |
| | THE STAIRS FROM THE EXTERIOR. |
| | |
| | 25) PLEASE EXPLAIN 20 MINUTE FIRE |
| | RATED DOORS AT ELEVATOR/LOBBY CORRIDOR. |
| | THESE DOORS ARE NOT THE SAME AS ENTRY |
| | DOORS TO APARTMENTS. |
| | |
| | 26) PLEASE INDICATE LOCATIONS OF ALL |
| | PORTABLE FIRE EXTINGUISHERS. |
| | |
| | 27) THERE APPEARS TO BE DOORS LOCATED |
| | WITHIN THE FOUR HOUR WALL ON PAGE |
| | A-2.7. ARE THESE DOORS PROPERLY RATED. |
| | |
| | 28) THE EXITING FIRE SPRINKLER AND |
| | LIFE SAFETY EQUIPMENT ARE TO REMAIN |
| | WHILE THE WEST TOWER IS UNDER |
| | CONSTRUCTION. |
| | |
| | 29) THE GARAGE IS PRESUMED TO REMAIN |
| | OCCUPIED WHILE THE WEST TOWER IS |
| | UNDER CONSTRUCTION. |
| | |
| | 30) THE EXITING DOOR AT THE TOP OF THE |
| | STAIRS NEAR THE AT&T ROOM SWINGS |
| | INWARD. THIS EXIT DOOR SHOULD IN THE |
| | DIRECTION OF EXIT TRAVEL. PLEASE |
| | REVISE PLANS. |
| | |
| | 31) PLEASE EXPLAIN WHY ON PAGE A-2.7 |
| | THERE APPEARS TO BE A DEAD-END |
| | CORRIDOR NEAR ELEVATOR # 1. |
| | |
| | 32) PLEASE DEMONSTRATE COMPLIANCE WITH |
| | ALL SECTIONS OF 412, OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 33) IS THE PROPOSED FIRE CONTROL ROOM |
| | LARGE ENOUGH TO CONTAIN ALL THE |
| | REQUIRED EQUIPMENT IN 412 OF THE |
| | FLORIDA BUILDING CODE, FIRE COMMAND |
| | ROOM. |
| | |
| | 34) ENSURE THAT DOORS FOR THE PROJECT |
| | SWING IN THE PROPER DIRECTION. |
| | |
| | 35) THE NEW FIRE ACCESS ROAD WILL |
| | SUPPORT HOW MUCH WEIGHT. |
| | |
| | 36) SOME EXISTING ROOMS ARE MISSING |
| | FIRE SPRINKLER HEADS NEAR PHASE I AND |
| | PHASE II ROOMS. |
| | |
| | 37) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR 3'- 6" HIGH |
| | GLASS RAILING SHOWN ON A-2.2. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |