Plan Review Notes
Plan Review Notes For Permit 04020684
Permit Number 04020684
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-04 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE FS 481.219, 471.023.
 PLANS REQ;D TO HAVE ALL LICENSE #'S
 AS REQ'D PER ABOVE ON TITLE BLOCKS PER
 FAC 61G15-23.002, 61G1-16.004
 THIS IS REQ'D FOR ARCH'S AND ENG'S.
 THIS IS ALSO REQ'D ON ALL SHEETS AND
 FOR ALL TRADES WEATHER OR NOT COMMENT
 IS MADE BY OTHERREVIEWERS.
  
 2)NOTE: PLEASE 110.26 FOR EXITING REQ'D
 FOR ELECTRICAL ROOMS. MIN.
  
 3)NOTE; PLEASE NOTE ON PLANS/RISER.
 TACTICAL SIGNAGE/MAPS BE REQ'D FOR FIRE
 PERSSONELL TO MAIN ELECTRICAL ROOMS.
 KNOX BOX FOR KEYS TO MAIN ELECTRICAL
 ROOMS.
  
 4)NOTE: PLEASE SEE CIRCUITING FOR SD'S
 IN UNITS. SHOWS SD'S ON MORE THAN ONE
 CIRCUIT. SD'D ARE REQ'D TO BE WIRED
 "INLINE", THIS WOULD CAUSE AN ELECTRIC-
 -AL PROBLEM ON MORE THAN ONE CIRCUIT.
 PLEASE SEE NFPA-72 8-1.4.2 FOR INSTALL-
 -ATION OF SD'S AND CLEARENCES FROM BATH
 / KITCHEN DOORS AND FROM KITCHEN COOKING
 APPLIANCES. A NOTE MAY BE ADDED FOR THIS
  
 5)NOTE: PLEASE SEE SOME UNITS DO NOT
 SEEM TO HAVE COMPLETED WALLS. DOES NOT
 SHOW RECEPTS REQUIRED FOR WALLS,210.52
 EGRESS LT CONTROL PER 210.70
 ETC.
  
 6)NOTE: PLEASE PROVIDE PLANS FOR
 EXISTING TOWER ELECTRICAL TO BRING UP TO
 2002 NEC PER FBC CHAPTER 34 FOR ADDITION
 -S TO EXISTING BLDGS.
  
 7)NOTE: PLEASE SEE UNIT "F" PANEL.
 SHOWS 164.9A'S W/ 200A OCP AND CONDUCTOR
 -S NOT RATED FOR 200A'S PER 310.16
  
 8)NOTE: PLEASE INDICATE OCP FOR EACH
 UNIT/PANEL. PLEASE CORRELATE OCP/AWG
  
 9)NOTE: PLEASE CLARFIY/SHOW EQUIPMENT
 GROUNDING CONDUCTORS REQ'D. 250.110
 250.24, SIZE PER 250.122
  
 10)NOTE: PLEASE SEE AIC RATINGS SHOWN
 FOR PANELS, SHOWS 100,000 RATED PANELS
 PLEASE VERFIY. IF SHOWN AS 100,000, THEN
 THATS WHAT WILL BE REQ'D TO BE INSTALLED
  
 11)NOTE: PLEASE SEE NOTES MENTION THAT
 ALUM CONDUCTORS AMY BE USED.
 PER LOCAL AMENDMENTS ALUM CONDUCTOR ARE
 NOT PERMITTED TO BE USED FOR GROUNDING
 OR BONDING. 310.2
 CONTRACTOR MAY ALSO NOT JUST CHANGE
 SIZES AND TYPE OF CONDUCTORS UNTIL PLANS
 ARE REVISED BY THE ENGINEER OF RECORD,
 SUBMITTED TO THE CITY OF WEST PALM BEACH
 FOR REVIEW AS A REVISION.
 PLEASE ADJUST NOTE.
  
 12)NOTE: PLEASE LIST/NOTE THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS PER 210.12
 ON PANEL SCHEDULES FOR UNITS.
  
 13)NOTE: PLEASE SEE LOAD SHOWN FOR
 PANELS "E" AND "F".
 LOAD CALCS SEEM TO BOTH FIGURED IN AS
 TYPICAL??
  
 14)NOTE: PLEASE PROVIDE OCP/ NOTE
 FOR MAIN FOR FIRE PUMP 695.4B1
  
 15)NOTE: PLEASE SEE EDP, PLEASE CORRE-
 -LATE OCP / AWG'S PER 310.16.
 WIRE SIZES ARE NOT RATED FOR OCP.
  
 PLANS SHOULD REFERENCE 2002 NEC
 PLEASE GO OVER PLANS FOR CODE COMPLIANCE
 BEFORE RESUBMITTING.
 PLANS WILL HAVE A ONE TIME RESUB @ NO
 CHARGE, EACH TIME THEREAFTER WILL BE A
 10% RESUB FEE.
  
 SEPARATION OF 4 HR FIRE WALL WILL BE
 REQUIRED BETWEEN NEW AND EXSITING IF
 CHAPTER 34 FBC IS NOT AN OPTION.
  
 COMPLETE ELECTRICAL REVIEW CAN NOT BE
 DONE AT THIS TIME DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]