| 2004-03-04 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FS 481.219, 471.023. |
| | PLANS REQ;D TO HAVE ALL LICENSE #'S |
| | AS REQ'D PER ABOVE ON TITLE BLOCKS PER |
| | FAC 61G15-23.002, 61G1-16.004 |
| | THIS IS REQ'D FOR ARCH'S AND ENG'S. |
| | THIS IS ALSO REQ'D ON ALL SHEETS AND |
| | FOR ALL TRADES WEATHER OR NOT COMMENT |
| | IS MADE BY OTHERREVIEWERS. |
| | |
| | 2)NOTE: PLEASE 110.26 FOR EXITING REQ'D |
| | FOR ELECTRICAL ROOMS. MIN. |
| | |
| | 3)NOTE; PLEASE NOTE ON PLANS/RISER. |
| | TACTICAL SIGNAGE/MAPS BE REQ'D FOR FIRE |
| | PERSSONELL TO MAIN ELECTRICAL ROOMS. |
| | KNOX BOX FOR KEYS TO MAIN ELECTRICAL |
| | ROOMS. |
| | |
| | 4)NOTE: PLEASE SEE CIRCUITING FOR SD'S |
| | IN UNITS. SHOWS SD'S ON MORE THAN ONE |
| | CIRCUIT. SD'D ARE REQ'D TO BE WIRED |
| | "INLINE", THIS WOULD CAUSE AN ELECTRIC- |
| | -AL PROBLEM ON MORE THAN ONE CIRCUIT. |
| | PLEASE SEE NFPA-72 8-1.4.2 FOR INSTALL- |
| | -ATION OF SD'S AND CLEARENCES FROM BATH |
| | / KITCHEN DOORS AND FROM KITCHEN COOKING |
| | APPLIANCES. A NOTE MAY BE ADDED FOR THIS |
| | |
| | 5)NOTE: PLEASE SEE SOME UNITS DO NOT |
| | SEEM TO HAVE COMPLETED WALLS. DOES NOT |
| | SHOW RECEPTS REQUIRED FOR WALLS,210.52 |
| | EGRESS LT CONTROL PER 210.70 |
| | ETC. |
| | |
| | 6)NOTE: PLEASE PROVIDE PLANS FOR |
| | EXISTING TOWER ELECTRICAL TO BRING UP TO |
| | 2002 NEC PER FBC CHAPTER 34 FOR ADDITION |
| | -S TO EXISTING BLDGS. |
| | |
| | 7)NOTE: PLEASE SEE UNIT "F" PANEL. |
| | SHOWS 164.9A'S W/ 200A OCP AND CONDUCTOR |
| | -S NOT RATED FOR 200A'S PER 310.16 |
| | |
| | 8)NOTE: PLEASE INDICATE OCP FOR EACH |
| | UNIT/PANEL. PLEASE CORRELATE OCP/AWG |
| | |
| | 9)NOTE: PLEASE CLARFIY/SHOW EQUIPMENT |
| | GROUNDING CONDUCTORS REQ'D. 250.110 |
| | 250.24, SIZE PER 250.122 |
| | |
| | 10)NOTE: PLEASE SEE AIC RATINGS SHOWN |
| | FOR PANELS, SHOWS 100,000 RATED PANELS |
| | PLEASE VERFIY. IF SHOWN AS 100,000, THEN |
| | THATS WHAT WILL BE REQ'D TO BE INSTALLED |
| | |
| | 11)NOTE: PLEASE SEE NOTES MENTION THAT |
| | ALUM CONDUCTORS AMY BE USED. |
| | PER LOCAL AMENDMENTS ALUM CONDUCTOR ARE |
| | NOT PERMITTED TO BE USED FOR GROUNDING |
| | OR BONDING. 310.2 |
| | CONTRACTOR MAY ALSO NOT JUST CHANGE |
| | SIZES AND TYPE OF CONDUCTORS UNTIL PLANS |
| | ARE REVISED BY THE ENGINEER OF RECORD, |
| | SUBMITTED TO THE CITY OF WEST PALM BEACH |
| | FOR REVIEW AS A REVISION. |
| | PLEASE ADJUST NOTE. |
| | |
| | 12)NOTE: PLEASE LIST/NOTE THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUITS PER 210.12 |
| | ON PANEL SCHEDULES FOR UNITS. |
| | |
| | 13)NOTE: PLEASE SEE LOAD SHOWN FOR |
| | PANELS "E" AND "F". |
| | LOAD CALCS SEEM TO BOTH FIGURED IN AS |
| | TYPICAL?? |
| | |
| | 14)NOTE: PLEASE PROVIDE OCP/ NOTE |
| | FOR MAIN FOR FIRE PUMP 695.4B1 |
| | |
| | 15)NOTE: PLEASE SEE EDP, PLEASE CORRE- |
| | -LATE OCP / AWG'S PER 310.16. |
| | WIRE SIZES ARE NOT RATED FOR OCP. |
| | |
| | PLANS SHOULD REFERENCE 2002 NEC |
| | PLEASE GO OVER PLANS FOR CODE COMPLIANCE |
| | BEFORE RESUBMITTING. |
| | PLANS WILL HAVE A ONE TIME RESUB @ NO |
| | CHARGE, EACH TIME THEREAFTER WILL BE A |
| | 10% RESUB FEE. |
| | |
| | SEPARATION OF 4 HR FIRE WALL WILL BE |
| | REQUIRED BETWEEN NEW AND EXSITING IF |
| | CHAPTER 34 FBC IS NOT AN OPTION. |
| | |
| | COMPLETE ELECTRICAL REVIEW CAN NOT BE |
| | DONE AT THIS TIME DUE TO PLANS NOT BEING |
| | COMPLETE AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |