| Plan Review Notes For Permit 04020656 |
| Permit Number |
04020656 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-03-16 00:00:00 | ****** UNSAT ***** | | | | | | 1)NOTE: PLEASE PROVIDE PANEL SCHEDULE | | | WITH ALL CIRCUITING TO CORRELATE WITH | | | BLDG CIRCUITS AS SHOWN. | | | PLEASE SHOW ALL CIRCUITING ON PLANS TO | | | CORRELATE WIHT THE PANEL SCHEDULE TO BE | | | SUBMITTED. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE IT SEEMS SOME | | | CIRCUITS MAY COME FROM MAIN BLDG AND DO | | | NOT INDICATE DISCONNECTING MEANS AS | | | REQUIRED PER 225.31-225.39 | | | THERE ARE SOME "KEY NOTES" WHICH | | | MENTIONS CIRCUITS FROM MAIN BLDG, | | | HOWEVER IT DOES NOT APPEAR INSTALLATION | | | AS SHOWN MEETS NEED NEC. | | | PLEASE PROVIDE A DETAIL FOR THIS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|