Plan Review Notes
Plan Review Notes For Permit 04020651
Permit Number 04020651
Review Stop E
Sequence Number 2
Notes
Date Text
2004-03-01 00:00:00*********** PROVISO/REVISION ******
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SEE AHU-2, STILL SHOWS
 50A OCP FOR 10KW HEAT. PLEASE SEE 424.3B
  
 2)NOTE: PLEASE SEE A/C LOAD SHOWN ON
 LOAD CALCULATIONS, SHOWN AT 40%. PLEASE
 SEE NEC 220, CAN NOT USE 40% FOR TWO
 UNITS, ONLY FOUR OR MORE. MAX WOULD BE
 65%. 220.30C
  
 3)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES.
 210.12B
  
 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE LOCAL AMENDMENTS,
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S INSIDE BUILDING. 230.70 AND 230.6
 NEC. 2" OF CONCRETE OR 18" BELOW BLDG.
  
 6)NOTE: KITCHEN SHOWS WHAT APPEARS TO BE
 A PENINSULAR? PLEASE SEE 210.52C, 210.8A
 -6.
  
 PLEASE REVISE PLANS ALONG WITH ANY OTHER
 CHANGES AND SUBMIT INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]