| 2004-03-01 00:00:00 | *********** PROVISO/REVISION ****** |
| | |
| | PLEASE SEE NOTES FROM FIRST REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE AHU-2, STILL SHOWS |
| | 50A OCP FOR 10KW HEAT. PLEASE SEE 424.3B |
| | |
| | 2)NOTE: PLEASE SEE A/C LOAD SHOWN ON |
| | LOAD CALCULATIONS, SHOWN AT 40%. PLEASE |
| | SEE NEC 220, CAN NOT USE 40% FOR TWO |
| | UNITS, ONLY FOUR OR MORE. MAX WOULD BE |
| | 65%. 220.30C |
| | |
| | 3)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULES. |
| | 210.12B |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2 |
| | SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| | |
| | 5)NOTE: PLEASE SEE LOCAL AMENDMENTS, |
| | NO MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| | -S INSIDE BUILDING. 230.70 AND 230.6 |
| | NEC. 2" OF CONCRETE OR 18" BELOW BLDG. |
| | |
| | 6)NOTE: KITCHEN SHOWS WHAT APPEARS TO BE |
| | A PENINSULAR? PLEASE SEE 210.52C, 210.8A |
| | -6. |
| | |
| | PLEASE REVISE PLANS ALONG WITH ANY OTHER |
| | CHANGES AND SUBMIT INFORMATION FOR |
| | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- |
| | -ION. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |