| 2004-02-17 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE 210.52D, 210.11C3 |
| | FOR MIN #12 AWG AND 20A FOR BATH(S), |
| | POWDER ROOM. |
| | |
| | 2)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU HEAT. PLEASE VERIFY KW RATING |
| | AT 10KW? |
| | PLEASE SEE LOAD CALCULATIONS. CALCS DO |
| | NOT INDICATE AHU/HEAT LOADS. |
| | |
| | 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | PLEASE CLARIFY IF KITCHEN IS SHOWING |
| | WHAT APPEARS TO BE A PENINSULAR.? |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE ALSO SEE ANY ROOMS THAT MAY |
| | CONTAIN CLOSETS/ BATHS ARE CONSIDERED |
| | TO BE ADAPTABLE SLEEPING RMS. |
| | PLEASE SEE FIRST FLR DEN/PLAYROOM. |
| | |
| | 5)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS |
| | 100A PANEL BEING FED FROM METER DIRECTLY |
| | TO 2ND FLOOR. PLEASE SEE 230.72 FOR |
| | GROUPING OF MAINS. |
| | IF PANEL "B" IS INDEED A SUB PANEL FROM |
| | PANEL "A", PLEASE INDICATE ON PANEL"A"'S |
| | PANEL SCHEDULE. OCP ETC. |
| | |
| | 6)NOTEL PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM PER 250.50. COLD WATER AND FOOTER |
| | STEEL. |
| | |
| | 7)NOTE:PLEASE SEE CU-2SHOWN ON PANEL |
| | SCHEDULE AS 1-P 15A ??? MISPRINT? |
| | |
| | 8)NOTE: PLEASE SEE LOCAL AMENDMENTS, |
| | NO MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| | -S(OCP) PERMITTED INSIDE BLDG. |
| | UNDER DWELLING IN CRAWL SPACE IS CONSID- |
| | -ERED INSIDE BLDG. |
| | A MEANS OF DISC AND OCP AT METER LOCAT- |
| | -ION. |
| | |
| | 9)NOTE: PLEASE SEE 225.31 FOR MEANS OF |
| | DISC REQ'D AT DETACHED STRUCTURE. |
| | PLEASE ALSO SEE 250.32 IF MORE THAN ONE |
| | CIRCUIT. PLEASE SEE LOAD IS SHOWN WITH |
| | MORE THAN ONE CIRCUIT. |
| | |
| | 10)NOTE: PLEASE LIST ALL CIRCUITS REQ'D |
| | WITH ARC FAULT PROTECTION ON PANEL |
| | SCHEDULE AND INDICATE AS SO. 210.12 OF |
| | THE 2002 NEC. |
| | |
| | 11)NOTE: PLEASE SEE MASTER BEDROOM, |
| | PLANS DO NOT INDICATE GFI FOR JACUZZI |
| | AS SHOWN ON PANEL SCHEDULE. |
| | |
| | 12)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | 2' OF WALL PER 210.52 MASTER BEDROOM. |
| | |
| | 13)NOTE: PLEASE SEE PANEL"A", NOTES ON |
| | LOWER LEFTHAND CORNER AS BEING MLO? YET, |
| | TOP OF PANEL INDICATES MAIN BRKR? |
| | PLEASE CORRELATE AND SEE COMMENT #8. |
| | |
| | 14)NOTE: PLEASE INCLUDE LICENSE # OF |
| | ARCH IN TITLE BLOCK. FAC 61G1-16.004 |
| | |
| | 15)NOTE: PLEASE INDICATE ALL GARAGE |
| | RECEPTS AS GFI/GFI PROTECTED. |
| | 210.82/ ALSO SHED/STORAGE BLDG. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |