Plan Review Notes
Plan Review Notes For Permit 04020639
Permit Number 04020639
Review Stop E
Sequence Number 5
Notes
Date Text
2006-02-22 00:00:00********** UNSAT ***********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES FOR ITEMS ON
 PLANS.
  
 1)NOTE:OK.
  
 2)NOTE: OK, GENERATOR REMOVED,HOWEVER
 LOAD CALCULATION OF SOME SORT SHOWN ON
 RISER WHICH IS UNCLEAR HOW THIS IS
 INCORPORATED INTO PLANS? 215.5
  
  
 3)NOTE: OK, HOWEVER PLEASE SEE ALMOST
 ALL BRANCH CIRCUITS IN PANEL INDICATE
 ARC FAULT PROTECTION?? PLEASE SEE BATH
 CIRCUITS? ETC. THE ONLY AREAS WHICH
 REQUIRE ARC FAULT IS BEDRM(S).
  
 4)NOTE: OK.
  
 5)NOTE:OK, HOWEVER, PLEASE SEE NO NEW
 DINING RM CIRCUITS ARE ON PANEL
 SCHEDULE? THERE IS HOWEVER TWO SMALL
 APPLIANCE CIRCUITS? ARE THESE THE
 "DINING RM CIRCUITS"?
  
 **PLEASE SEE NEW DINING AREA CALLS
 FOR DEDICATED DINING BRANCH CIRCUITS AS
 REQUIRED UNDER 210.52B1, 210.11,220.16
 MUIST BE 20A AND #12.
  
 6)NOTE: NO, PLEASE SEE NOW LOAD
 CALCULATIONS INDICATE TWO LOADS FOR
 DRYERS AT 5KW, HOWEVER PANEL SCHEDULE
 ONLY INDICATES A 1-POLE 20A OCP FOR THIS
 ON THE STACKABLE UNIT? PLEASE SEE #10
 AWG IS SHOWN.
 PLEASE ALSO SEE LOAD CALCULATIONS FOR
 SERVICE DO NOT CORRELATE WITH THIS??
 PLEASE SEE LOAD CALCULATION COMMENT
 BELOW.
  
 ** PLEASE SEE PLANS CALL FOR A NEW
 WASHER AND DRYER LOCATE DON 1ST FLR AND
 ALSO A NEW STACKABLE UNIT ON 2ND FLR,
 HOWEVER PANEL SCHEDULE ONLY INDICATES
 ONE DRYER? GAS?
  
 **PLEASE SEE 220.16, 210.11C WHICH
 REQUIRES A MIN OF 1.5KW FOR LAUNDRY
 CIRCUIT, WASHER,ETC.
 PLEASE SEE 220.18 FOR A MIN OF 5KW TO BE
 FIGURED FOR DRYER(S).
 PLEASE ALSO NOTE OF EXISTING IN MAIN
 HOUSE ARE BEING REMOVED OR RELOCATED.
 PLEASE ADJUST LOAD CALCULATIONS AND
 CORRELATE.
 215.5,
  
 7)NOTE: NO, PLEASE SEE NOTES ABOVE AND
 PLEASE SEE LOAD CALCS.
 PLEASE ALSO INDICATE WHAT THW % FOR AHU
 HEAT LOADS.PLEASE SEE LOAD CALC AS
 NOTED ON FUTURE GEN PANEL SHOWS AHU AT
 10KW, LOAD ON PANEL "C" SHOWS 5.5KW,
 WHERE AND WHAT OTHER A/C HEAT LOADS ARE
 THERE?
  
 ** PLEASE SEE ALL LOAD CALCULATIONS
 SHALL BE FIGURED PER 220.31B FOR
 ADDITONS TO EXISITING DWELLINGS.
  
 8)NOTE: NO, PLEASE KNOW, PLANS WERE GONE
 OVER IN LOBBY IN A BRIEF REVIEW OF
 NOTES, AND IT WAS MENTIONED TO
 CONTRACTOR THAT THE "EQUIPMENT GROUNDING
 CONDUCTORS" WERE STILL BEING SHOWN,
 HOWEVER NOW PLANS HAVE COME BACK WITH
 WHITE-OUT ON RISER REMOVING ALL SEC'S???
 PLEASE SHOW THE CORRECT SEC'S FROM
 GUTTER TO EACH MAIN.
  
 ** PLEASE SEE SEC'S TO MAIN GUTTER
 INDICATE SERVICE AS A 3-PHASE SERVICE??
 PLEASE ALSO SEE AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS STILL BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24 WHICH ONLY
 PERMITS THE EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 9)NOTE: OK, PLEASE RE-PRINT WITH OUT
 WHITE-OUT.
  
 ** PLEASE SEE 310.15B6, 250.66 FOR
 THE MIN SIZE FOR THE GROUNDING ELECTRODE
 CONDUCTOR. 1/0 MIN.
 THIS SHALL ALSO INCLUDE ATTACHEMENT TO
 THE NEW FOOTER STEEL AS REQUIRED PER
 250.50
  
 10)NOTE:OK
  
 11)NOTE:OK.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]