| Date |
Text |
| 2006-02-22 00:00:00 | ********** UNSAT *********** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES FOR ITEMS ON |
| | PLANS. |
| | |
| | 1)NOTE:OK. |
| | |
| | 2)NOTE: OK, GENERATOR REMOVED,HOWEVER |
| | LOAD CALCULATION OF SOME SORT SHOWN ON |
| | RISER WHICH IS UNCLEAR HOW THIS IS |
| | INCORPORATED INTO PLANS? 215.5 |
| | |
| | |
| | 3)NOTE: OK, HOWEVER PLEASE SEE ALMOST |
| | ALL BRANCH CIRCUITS IN PANEL INDICATE |
| | ARC FAULT PROTECTION?? PLEASE SEE BATH |
| | CIRCUITS? ETC. THE ONLY AREAS WHICH |
| | REQUIRE ARC FAULT IS BEDRM(S). |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE:OK, HOWEVER, PLEASE SEE NO NEW |
| | DINING RM CIRCUITS ARE ON PANEL |
| | SCHEDULE? THERE IS HOWEVER TWO SMALL |
| | APPLIANCE CIRCUITS? ARE THESE THE |
| | "DINING RM CIRCUITS"? |
| | |
| | **PLEASE SEE NEW DINING AREA CALLS |
| | FOR DEDICATED DINING BRANCH CIRCUITS AS |
| | REQUIRED UNDER 210.52B1, 210.11,220.16 |
| | MUIST BE 20A AND #12. |
| | |
| | 6)NOTE: NO, PLEASE SEE NOW LOAD |
| | CALCULATIONS INDICATE TWO LOADS FOR |
| | DRYERS AT 5KW, HOWEVER PANEL SCHEDULE |
| | ONLY INDICATES A 1-POLE 20A OCP FOR THIS |
| | ON THE STACKABLE UNIT? PLEASE SEE #10 |
| | AWG IS SHOWN. |
| | PLEASE ALSO SEE LOAD CALCULATIONS FOR |
| | SERVICE DO NOT CORRELATE WITH THIS?? |
| | PLEASE SEE LOAD CALCULATION COMMENT |
| | BELOW. |
| | |
| | ** PLEASE SEE PLANS CALL FOR A NEW |
| | WASHER AND DRYER LOCATE DON 1ST FLR AND |
| | ALSO A NEW STACKABLE UNIT ON 2ND FLR, |
| | HOWEVER PANEL SCHEDULE ONLY INDICATES |
| | ONE DRYER? GAS? |
| | |
| | **PLEASE SEE 220.16, 210.11C WHICH |
| | REQUIRES A MIN OF 1.5KW FOR LAUNDRY |
| | CIRCUIT, WASHER,ETC. |
| | PLEASE SEE 220.18 FOR A MIN OF 5KW TO BE |
| | FIGURED FOR DRYER(S). |
| | PLEASE ALSO NOTE OF EXISTING IN MAIN |
| | HOUSE ARE BEING REMOVED OR RELOCATED. |
| | PLEASE ADJUST LOAD CALCULATIONS AND |
| | CORRELATE. |
| | 215.5, |
| | |
| | 7)NOTE: NO, PLEASE SEE NOTES ABOVE AND |
| | PLEASE SEE LOAD CALCS. |
| | PLEASE ALSO INDICATE WHAT THW % FOR AHU |
| | HEAT LOADS.PLEASE SEE LOAD CALC AS |
| | NOTED ON FUTURE GEN PANEL SHOWS AHU AT |
| | 10KW, LOAD ON PANEL "C" SHOWS 5.5KW, |
| | WHERE AND WHAT OTHER A/C HEAT LOADS ARE |
| | THERE? |
| | |
| | ** PLEASE SEE ALL LOAD CALCULATIONS |
| | SHALL BE FIGURED PER 220.31B FOR |
| | ADDITONS TO EXISITING DWELLINGS. |
| | |
| | 8)NOTE: NO, PLEASE KNOW, PLANS WERE GONE |
| | OVER IN LOBBY IN A BRIEF REVIEW OF |
| | NOTES, AND IT WAS MENTIONED TO |
| | CONTRACTOR THAT THE "EQUIPMENT GROUNDING |
| | CONDUCTORS" WERE STILL BEING SHOWN, |
| | HOWEVER NOW PLANS HAVE COME BACK WITH |
| | WHITE-OUT ON RISER REMOVING ALL SEC'S??? |
| | PLEASE SHOW THE CORRECT SEC'S FROM |
| | GUTTER TO EACH MAIN. |
| | |
| | ** PLEASE SEE SEC'S TO MAIN GUTTER |
| | INDICATE SERVICE AS A 3-PHASE SERVICE?? |
| | PLEASE ALSO SEE AN "EQUIPMENT GROUNDING |
| | CONDUCTOR" IS STILL BEING SHOWN BEFORE |
| | THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6, 250.24 WHICH ONLY |
| | PERMITS THE EQUIPMENT GROUNDING |
| | CONDUCTOR AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 9)NOTE: OK, PLEASE RE-PRINT WITH OUT |
| | WHITE-OUT. |
| | |
| | ** PLEASE SEE 310.15B6, 250.66 FOR |
| | THE MIN SIZE FOR THE GROUNDING ELECTRODE |
| | CONDUCTOR. 1/0 MIN. |
| | THIS SHALL ALSO INCLUDE ATTACHEMENT TO |
| | THE NEW FOOTER STEEL AS REQUIRED PER |
| | 250.50 |
| | |
| | 10)NOTE:OK |
| | |
| | 11)NOTE:OK. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |