| Plan Review Notes For Permit 04020639 |
| Permit Number |
04020639 |
|
| Review Stop |
Z |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-01-11 00:00:00 | DENIED, | | | 1. MUST SUBMIT THE TWO COPY OF SURVEY | | | SHOWING THE PROPOSED ADDITION (SURVEY | | | NOT ENCLOSED). | | | 2. NEED EXPLAINATION TO WHAT IS EX. REF( | | | A-1)? A SECOND REF CAN ONLY BE AN U/C | | | REF.(MUST SHOW ON PLANS AS A U/C REF). | | | OLD PLANS SHOWS STAIRS AND THIS IS A NEW | | | PROPOSED 2 STORY STRUCTURE. | | | 3. PLEASE EXPLAIN FIREPLACE? ON A-1 EX. | | | FAMILY ROOM. | | | 4. 2ND FLOOR PLANS (A-1) SHOWS WHAT | | | LOOKS LIKE AN ACESS, PLEASE CLARIFY. | | | 5. A-1 SECOND FLOORS 3 S-4 SHOWS A SOLID | | | WALL, PLEASE CLARIFY? | | | 6. THE PROPOSED 2ND STORY CAN ONLY BE A | | | MAXIMUM OF 30FT HIGH.PLANS SHOWS | | | 34/35+ FEET HIGH.IF CHIMENY TO BE | | | ADDED (WITH PLANS SHOWING) THE HEIGHT | | | CAN BE 33FT (30 + 10%) = 33FT. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|