Plan Review Notes
Plan Review Notes For Permit 04020639
Permit Number 04020639
Review Stop P
Sequence Number 4
Notes
Date Text
2006-03-01 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM IS NOT TO CODE.
 A)AUTOMATIC CLOTHES WASHER IS NOT
 VENTED, AND A CLEANOUT IS REQUIRED TO BE
 48" ABOVE FINISH FLOOR.
 B)HORIZONTAL DRY VENTS ARE NOT
 PERMITED. SEC.905.3
 C)AUTO MATIC CLOTHES WASHER AND
 LOUNDRY TUB MUST DISCHARGE DOWN STREAM
 OF THE BATHROOM GROUP. SEC.909.1.
 D) LAV. IS NOT VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695