Plan Review Notes
Plan Review Notes For Permit 04020639
Permit Number 04020639
Review Stop E
Sequence Number 4
Notes
Date Text
2006-01-18 00:00:00*********** UNSAT ***********
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 THERE HAVE BEEN MANY CHANGES TO PLANS .
  
  
 1)NOTE: PLEASE COMPLETE ALL INFORMATION
 ON ALL TITLE BLOCKS ON SAID PLANS PER
 FLORIDA ADMIN CODE. 61G1-16.004.
 PLEASE SEE FBC 104.2.1 WHICH REQUIRES
 ALL PLANS TO CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR SAID PLANS/DESIGN. PLEASE KNOW, ALL
 PLANS WOULD ALSO BE REQUIRED TO BE
 SIGNED, DATED AND SEALED BY ANY
 ARCHITECT'S RESPONSIBLE FOR DESIGN.
 FS 481.221
 PLEASE SEE OTHER SHEETS APPEAR TO BE
 SIGNED WITH "INITIALS"? IF INDEED THIS
 IS THE LEGAL SIGNATURE OF THE ARCHITECT,
 PLEASE PROVIDE AND SIGNED, DATED AND
 SEALED LETTER WITH REFERENCE TO THE
 LEGAL SIGNATURE.( PLEASE BE SURE LTR IS
 CORRECTLY NOTORIZED UNDER FS 117.05).
  
 ** PLEASE KNOW, THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT(S) ARE MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SEE RISER NOW INDICATES A
 NEW GENERATOR/ ATS ETC. PLEASE KNOW, A
 SEPARATE PERMIT IS REQUIRED FOR THE GEN
 ETC AND MUST SUBMIT PLANS, PERMIT APPL,
 SPECS, SURVEY ETC.
 PLEASE SEE ALL OF 225.31-225.39 FOR
 DISCONNECTING MEANS OF FEEDERS COMING
 FROM GEN, GROUPING WITH EXISTING, RATED
 FOR THE LOAD SERVED, SERVICE RATED ETC.
 PLEASE BEAR IN MIND, PLANS MAY NOT
 INCLUDE GENERATOR UNTIL SUCH TIME GEN
 PERMIT IS ISSUED.
  
  
 3)NOTE: PLEASE SEE ORIGINAL PLANS WERE
 REDLINED FOR 2002 NEC 210.12 WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 "OUTLETS" IN BEDRM AREAS. PLEASE SEE
 DOWNSTAIRS IS NOW CHANGED TO A DINING
 AREA AND UPSTAIRS IS NOTED AS FUTURE
 BEDRM.
 PLEASE IST THE REQUIRED ARC FAULT FOR
 ALL, SD'S, LTS, FANS, RECEPTS ETC.
 PLEASE LIST THESE REQUIRED CIRCUITS ON
 PANEL SCHEDULE.
  
 4)NOTE: RISER CALLS FOR A NEW PANEL "C",
 HOWEVER THIS PANEL COULD NOT BE LOCATED
 ON PLANS.
 215.5, 240.24, 408.7,110.26 ETC
  
 5)NOTE: PLEASE SEE NEW DINING AREA CALLS
 FOR DEDICATED DINING BRANCH CIRCUITS AS
 REQUIRED UNDER 210.52B1, 210.11,220.16
 MUIST BE 20A AND #12.
  
 6)NOTE: PLEASE SEE PLANS CALL FOR A NEW
 WASHER AND DRYER LOCATE DON 1ST FLR AND
 ALSO A NEW STACKABLE UNIT ON 2ND FLR,
 HOWEVER PANEL SCHEDULE ONLY INDICATES
 ONE DRYER?
 PLEASE SEE 220.16, 210.11C WHICH
 REQUIRES A MIN OF 1.5KW FOR LAUNDRY
 CIRCUIT, WASHER,ETC.
 PLEASE SEE 220.18 FOR A MIN OF 5KW TO BE
 FIGURED FOR DRYER(S).
 PLEASE ALSO NOTE OF EXISTING IN MAIN
 HOUSE ARE BEING REMOVED OR RELOCATED.
 PLEASE ADJUST LOAD CALCULATIONS AND
 CORRELATE.
 215.5,
  
 7)NOTE: PLEASE SEE ALL LOAD CALCULATIONS
 SHALL BE FIGURED PER 220.31B FOR
 ADDITONS TO EXISITING DWELLINGS.
  
 8)NOTE: PLEASE SEE SEC'S TO MAIN GUTTER
 INDICATE SERVICE AS A 3-PHASE SERVICE??
 PLEASE ALSO SEE AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS STILL BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24 WHICH ONLY
 PERMITS THE EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 9)NOTE: PLEASE SEE 310.15B6, 250.66 FOR
 THE MIN SIZE FOR THE GROUNDING ELECTRODE
 CONDUCTOR. 1/0 MIN.
 THIS SHALL ALSO INCLUDE ATTACHEMENT TO
 THE NEW FOOTER STEEL AS REQUIRED PER
 250.50
  
 10)NOTE: PLEASE SEE 210.8A2 FOR ALL
 RECEPTS LOCATED IN GARAGE SHALL BE SHOWN
 AS GFI/.
  
 11)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT SPACING AS REQUIRED.
 PLEASE SEE PLANS HAVE BEEN REDLINED AT
 LOCATIONS.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]