| 2006-01-18 00:00:00 | *********** UNSAT *********** |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS AS |
| | THERE HAVE BEEN MANY CHANGES TO PLANS . |
| | |
| | |
| | 1)NOTE: PLEASE COMPLETE ALL INFORMATION |
| | ON ALL TITLE BLOCKS ON SAID PLANS PER |
| | FLORIDA ADMIN CODE. 61G1-16.004. |
| | PLEASE SEE FBC 104.2.1 WHICH REQUIRES |
| | ALL PLANS TO CONTAIN THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR SAID PLANS/DESIGN. PLEASE KNOW, ALL |
| | PLANS WOULD ALSO BE REQUIRED TO BE |
| | SIGNED, DATED AND SEALED BY ANY |
| | ARCHITECT'S RESPONSIBLE FOR DESIGN. |
| | FS 481.221 |
| | PLEASE SEE OTHER SHEETS APPEAR TO BE |
| | SIGNED WITH "INITIALS"? IF INDEED THIS |
| | IS THE LEGAL SIGNATURE OF THE ARCHITECT, |
| | PLEASE PROVIDE AND SIGNED, DATED AND |
| | SEALED LETTER WITH REFERENCE TO THE |
| | LEGAL SIGNATURE.( PLEASE BE SURE LTR IS |
| | CORRECTLY NOTORIZED UNDER FS 117.05). |
| | |
| | ** PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT(S) ARE MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE RISER NOW INDICATES A |
| | NEW GENERATOR/ ATS ETC. PLEASE KNOW, A |
| | SEPARATE PERMIT IS REQUIRED FOR THE GEN |
| | ETC AND MUST SUBMIT PLANS, PERMIT APPL, |
| | SPECS, SURVEY ETC. |
| | PLEASE SEE ALL OF 225.31-225.39 FOR |
| | DISCONNECTING MEANS OF FEEDERS COMING |
| | FROM GEN, GROUPING WITH EXISTING, RATED |
| | FOR THE LOAD SERVED, SERVICE RATED ETC. |
| | PLEASE BEAR IN MIND, PLANS MAY NOT |
| | INCLUDE GENERATOR UNTIL SUCH TIME GEN |
| | PERMIT IS ISSUED. |
| | |
| | |
| | 3)NOTE: PLEASE SEE ORIGINAL PLANS WERE |
| | REDLINED FOR 2002 NEC 210.12 WHICH |
| | REQUIRES ARC FAULT PROTECTION FOR ALL |
| | "OUTLETS" IN BEDRM AREAS. PLEASE SEE |
| | DOWNSTAIRS IS NOW CHANGED TO A DINING |
| | AREA AND UPSTAIRS IS NOTED AS FUTURE |
| | BEDRM. |
| | PLEASE IST THE REQUIRED ARC FAULT FOR |
| | ALL, SD'S, LTS, FANS, RECEPTS ETC. |
| | PLEASE LIST THESE REQUIRED CIRCUITS ON |
| | PANEL SCHEDULE. |
| | |
| | 4)NOTE: RISER CALLS FOR A NEW PANEL "C", |
| | HOWEVER THIS PANEL COULD NOT BE LOCATED |
| | ON PLANS. |
| | 215.5, 240.24, 408.7,110.26 ETC |
| | |
| | 5)NOTE: PLEASE SEE NEW DINING AREA CALLS |
| | FOR DEDICATED DINING BRANCH CIRCUITS AS |
| | REQUIRED UNDER 210.52B1, 210.11,220.16 |
| | MUIST BE 20A AND #12. |
| | |
| | 6)NOTE: PLEASE SEE PLANS CALL FOR A NEW |
| | WASHER AND DRYER LOCATE DON 1ST FLR AND |
| | ALSO A NEW STACKABLE UNIT ON 2ND FLR, |
| | HOWEVER PANEL SCHEDULE ONLY INDICATES |
| | ONE DRYER? |
| | PLEASE SEE 220.16, 210.11C WHICH |
| | REQUIRES A MIN OF 1.5KW FOR LAUNDRY |
| | CIRCUIT, WASHER,ETC. |
| | PLEASE SEE 220.18 FOR A MIN OF 5KW TO BE |
| | FIGURED FOR DRYER(S). |
| | PLEASE ALSO NOTE OF EXISTING IN MAIN |
| | HOUSE ARE BEING REMOVED OR RELOCATED. |
| | PLEASE ADJUST LOAD CALCULATIONS AND |
| | CORRELATE. |
| | 215.5, |
| | |
| | 7)NOTE: PLEASE SEE ALL LOAD CALCULATIONS |
| | SHALL BE FIGURED PER 220.31B FOR |
| | ADDITONS TO EXISITING DWELLINGS. |
| | |
| | 8)NOTE: PLEASE SEE SEC'S TO MAIN GUTTER |
| | INDICATE SERVICE AS A 3-PHASE SERVICE?? |
| | PLEASE ALSO SEE AN "EQUIPMENT GROUNDING |
| | CONDUCTOR" IS STILL BEING SHOWN BEFORE |
| | THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6, 250.24 WHICH ONLY |
| | PERMITS THE EQUIPMENT GROUNDING |
| | CONDUCTOR AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 9)NOTE: PLEASE SEE 310.15B6, 250.66 FOR |
| | THE MIN SIZE FOR THE GROUNDING ELECTRODE |
| | CONDUCTOR. 1/0 MIN. |
| | THIS SHALL ALSO INCLUDE ATTACHEMENT TO |
| | THE NEW FOOTER STEEL AS REQUIRED PER |
| | 250.50 |
| | |
| | 10)NOTE: PLEASE SEE 210.8A2 FOR ALL |
| | RECEPTS LOCATED IN GARAGE SHALL BE SHOWN |
| | AS GFI/. |
| | |
| | 11)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPT SPACING AS REQUIRED. |
| | PLEASE SEE PLANS HAVE BEEN REDLINED AT |
| | LOCATIONS. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |