| Plan Review Notes For Permit 04020639 |
| Permit Number |
04020639 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-10-06 00:00:00 | *** PLEASE SEE ALL NEW ELECTRICAL SHEETS | | | SUBMITTED. | | | | | | ** PLANS REDLINED *** | | | | | | 1)NOTE: PLEASE SEE RISER STILL SHOWS | | | EQUIPMENT GROUNDING CONDUCTORS FROM | | | METER TO GUTTER AND GUTTER TO EACH MAIN | | | DISC?? | | | EQUIPMENT GROUNDING IS ONLY INSTALL | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | PLEASE SEE 250.6,250.24. | | | | | | 2)NOTE: CABANA REQUIRED TO HAVE SD | | | WIRED IN-LINE WITH OTHERS. | | | | | | 3)NOTE: PLEASE SEE CABANA ALSO REQUIRED | | | TO HAVE ARC-FAULT PROTECTION FOR RECEPTS | | | ,SD'S AND LTS. 210.12 2002 NEC. |
|