Plan Review Notes
Plan Review Notes For Permit 04020639
Permit Number 04020639
Review Stop E
Sequence Number 3
Notes
Date Text
2004-10-06 00:00:00*** PLEASE SEE ALL NEW ELECTRICAL SHEETS
 SUBMITTED.
  
 ** PLANS REDLINED ***
  
 1)NOTE: PLEASE SEE RISER STILL SHOWS
 EQUIPMENT GROUNDING CONDUCTORS FROM
 METER TO GUTTER AND GUTTER TO EACH MAIN
 DISC??
 EQUIPMENT GROUNDING IS ONLY INSTALL
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24.
  
 2)NOTE: CABANA REQUIRED TO HAVE SD
 WIRED IN-LINE WITH OTHERS.
  
 3)NOTE: PLEASE SEE CABANA ALSO REQUIRED
 TO HAVE ARC-FAULT PROTECTION FOR RECEPTS
 ,SD'S AND LTS. 210.12 2002 NEC.