| Plan Review Notes For Permit 04020639 |
| Permit Number |
04020639 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-21 00:00:00 | PROVISO: | | | PLAN 6 OF 7 INDICATES AN OVERFLOW PAN | | | BUT DOES NOT INDICATE SECONDARY DRAIN | | | LINE OR FLOAT SWITCH.PER 2001 FBC(M) | | | 307.2.3, A SECONDARY DRAIN LINE SHALL | | | TERMINATE A CONSPICUOUS POINT TO SERVE | | | AS AN ALARM THAT THE PRIMARY DRAIN IS | | | RESTRICTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|