2004-10-21 00:00:00PROVISO:
 PLAN 6 OF 7 INDICATES AN OVERFLOW PAN
 BUT DOES NOT INDICATE SECONDARY DRAIN
 LINE OR FLOAT SWITCH.PER 2001 FBC(M)
 307.2.3, A SECONDARY DRAIN LINE SHALL
 TERMINATE A CONSPICUOUS POINT TO SERVE
 AS AN ALARM THAT THE PRIMARY DRAIN IS
 RESTRICTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.