Text |
| 2004-02-24 00:00:00 | *************** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE RISER, RISER NOW |
| | SHOWS REMOVING FEED FROM METER TO BOTH |
| | PANELS, YET NO NEW FEED IS SHOWNTO |
| | GUTTER? PLEASE INDICATE , CONDUITS,AWG |
| | ETC. 215.5 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 NEW MAIN. |
| | |
| | 3)NOTE: : PLEASE SEE 250.24, AN EQUIP- |
| | -MENT GROUNDING CONDUCTOR IS ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF DISC- |
| | -ONNECT. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 6))NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 8)NOTE: PLEASE CLARIFY SECOND A/C COND |
| | UNIT SHOWN. IS THIS FOR AN EXISTING |
| | SYSTEM ON MAIN HOUSE? |
| | PLEASE SEE PANEL SCHEDULE, SHOWS A |
| | SECOND A/C SYSTEM,BOTH AS 1-POLE |
| | CIRCUITS, 15A OCP AND #14 AWG?? |
| | |
| | 9) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |