2004-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 4) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 5) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6) SHEET 6 OF 6 STATES - NOTE: THIS
 SHEET IS NOT VALID UNLESS USED WITH PAGE
 1. PLEASE CLAIRFY THIS NOTE.
 7) FILTER AND PIPING ISOMETRIC SHEET
 SHALL BE SIGNED, SEALED & DATED BY THE
 ENGINEER OF RECORD. THIS SHEET IS JUST A
 COPY OF SIGNATURE AND SEAL IS NOT RAISED
 FS 471.025
  