2004-03-12 00:00:00APPROVED PROVISO:
  
 1) THE GALLERY DESIGN SHOULD BE
 RECONSIDERED BY THE DESIGN TEAM. THE
 INTENT WAS TO BE ABLE TO PROVIDE EXIT
 DISCHARGE FROM THE GALLERY AREA IN THE
 EVENT OF A FIRE. REVISION # 6 INDICATES
 THAT "EMERGENCY EXIT HARDWARE ON
 POOL BARRIER FENCE GATE". AFTER
 CONSIDERING THIS INFORMATION, IT
 WAS REALIZED THAT A CHILD COULD
 LEAVE THE GALLERY AND USE THE EXIT
 HARDWARE AND BE INJURED OR WORSE BY
 THE POOL. WRITER CONTACTED DOUG
 WALKER OF TSENG CONSULTING GROUP
 AND EXPLAINED THE ISSUE TO HIM. HE
 EXPLAINED THAT THE TYPICAL GATE
 HARDWARE IS MOUNTED AT 54" INCH WHICH
 WOULD NOT BE POSSIBLE ON 48" GATE.
 DOUG WALKER CALLED BACK AND ADVISED
 THAT A REDESIGN WOULD BE OCCURRING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910